AL
— Alarm Relay Contacts
ASTAT
— Aquastat
BR
— Blower Relay
CB
— Circuit Breaker
CC
— Compressor Contactor
CO
— Condensate Overflow Sensor
COMPR — Compressor
DTS
— Discharge Temp Switch
FP1
— Water Coil Freeze Protection Sensor
FP2
— Air Coil Freeze Protection Sensor
HP
— High-Pressure Switch
HWG
— Hot Water Generator
JW
— Jumper Wire
LOC
— Loss of Charge Pressure Switch
MV
— Motorized Valve
NEC
— National Electrical Code
PSC
— Permanent Split Capacitor
P1
— Field Wiring Terminal Block
RVS
— Reversing Valve Solenoid
*Optional.
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. 208/230 v transformer will be connected for 208 v operation. For
230 v operation, disconnect RED lead at L1 and attach ORANGE
lead to L1. Insulate open end of RED lead. Transformer is energy
limiting or may have circuit breaker.
4. FP1 thermistor provides freeze protection for water. When using
antifreeze solutions, cut JW3 jumper.
5. Check installation wiring information for specific thermostat hookup.
Refer to thermostat installation instructions for wiring to the unit.
Thermostat wiring must be "Class 1" and voltage rating equal to or
greater than unit supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper
and dry contact will be available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs and
screws to control box. (Ground available from top two standoffs as
shown.)
8. Aquastat is supplied with unit and must be wired in series with the
hot leg to the pump. Aquastat is rated for voltage up to 277 v.
9. Fan motors factory wired for medium speed. For high and low speed
remove BLU wire from fan motor speed tap 'M' and connect to 'H'
for high or 'L' for low.
TRANS — Transformer
UPS
Fig. 15 — Units with Complete C Controller, Single-Phase
LEGEND
— Unit Performance Sentinel
Factory Low Voltage Wiring
Factory Line Voltage Wiring
Field Low Voltage Wiring
Field Line Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Thermistor
Condensate Pan
Circuit Breaker
COMPLETE C CONTROLLER FAULT CODES
DESCRIPTION OF OPERATION
Normal Mode
Normal Mode with UPS Warning
Complete C is Non-Functional
Fault Retry
Lockout
Over/Under Voltage Shutdown
Test Mode-No Fault in Memory
Test Mode-HP Fault in Memory
Test Mode-LP Fault in Memory
Test Mode-FP1 Fault in Memory
Test Mode-FP2 Fault in Memory
Test Mode-CO Fault in Memory
Test Mode-Over/Under Shutdown
in Memory
Test Mode-UPS in Memory
Swapped FP1/FP2 Lockout
14
Solenoid Coil
Relay Contacts - N.C.
Relay Contacts - N.O.
Capacitor
Temperature Switch
Low Pressure Switch
High Pressure Switch
Wire Nut
Splice Cap
LED
G
LED
ALARM RELAY
ON
Open
Cycle (Closed 5 Sec.
ON
Open 25 Sec.)
OFF
Open
Slow Flash
Open
Fast Flash
Closed
Open
Slow Flash
(Closed After 15 Min.)
Flashing Code 1
Cycling Code 1
Flashing Code 2
Cycling Code 2
Flashing Code 3
Cycling Code 3
Flashing Code 4
Cycling Code 4
Flashing Code 5
Cycling Code 5
Flashing Code 6
Cycling Code 6
Flashing Code 7
Cycling Code 7
Flashing Code 8
Cycling Code 8
Flashing Code 9
Cycling Code 9