Start-Up; Preliminary Checks; Evacuate And Dehydrate; Refrigerant Charge - Carrier AIR COOLED SPLIT SYSTEM 38AQS008 Installation And Service Instructions Manual

Air-cooled split system heat pump 50/60 hz
Hide thumbs Also See for AIR COOLED SPLIT SYSTEM 38AQS008:
Table of Contents

Advertisement

START-UP

Preliminary Checks

1. Check that all internal wiring connections are tight and
that all barriers, covers, and panels are in place.
2. Field electrical power source must agree with unit name-
plate rating.
3. Ensure all service valves are open. Ensure all compressor
service valves are backseated.
4. Verify that compressor holddown bolts have been loos-
ened and that flat/snubber washers can be rotated by fin-
ger pressure (snug, but not tight).
5. Verify compressor crankcase heater is securely in place.
Crankcase heater must operate for at least 24 hours be-
fore start-up.
6. Note that compressor oil level is visible in the sight glass.
7. Check for leaks in refrigerant system by using soap bubbles
and/or electronic leak detector.
8. Check voltage imbalance as shown in Table 4, Note 2.
9. Check that both outdoor and indoor units are properly
mounted in accordance with installation instructions and
applicable codes.
Evacuate and Dehydrate —
entire refrigerant system by use of the methods
described in Carrier GTAC II, Module 4, System
Dehydration.
Refrigerant Charge —
ule 5, Charging Recovery, Recycling, and Reclamation.
NOTE: Use of a Carrier Totalclaim refrigeration recovery
unit is highly recommended when recovering refrigerant.
Unit panels must be in place when unit is operating dur-
ing charging procedure.
Unit is shipped with holding charge only. Weigh in 15 lb
(7 kg) of R-22 to start unit.
CHARGE COOLING — Use Cooling Charging Chart (see
Fig. 11). Vary refrigerant until the conditions of the chart are
met. Note that charging chart is different from the type nor-
mally used. Chart is based on charging the units to the cor-
rect subcooling for the various operating conditions. Accu-
rate pressure gage and temperature sensing device are required.
Connect the pressure gage to the service port on the liquid
line service valve. Mount the temperature sensing device on
the liquid line, close to the liquid line service valve, and in-
sulate it so that outdoor ambient temperature does not affect
the reading. Indoor airflow must be within the normal op-
erating range of the unit.
Operate unit a minimum of 15 minutes. Ensure pressure
and temperature readings have stabilized. Plot liquid pres-
sure and temperature on chart and add or reduce charge to
meet curve. Adjust charge to conform with charging chart,
using liquid pressure and temperature to read chart.
OIL CHARGE (Tables 1A and 1B) — Allow unit to run for
about 20 minutes. Stop unit and check compressor oil level.
Add oil only if necessary to bring oil into view in sight glass.
Use only Carrier-approved compressor oil.
Approved oils are:
Suniso 3GS and WF32-150

Evacuate and dehydrate

Refer to Carrier GTAC II, Mod-
Fig. 11 — Cooling Charging Chart — 38AQS008
Do not reuse drained oil or use any oil that has been ex-
posed to atmosphere. Procedures for adding or removing oil
are given in Carrier's Refrigerant Service Techniques manual.
If oil is added, run unit for additional 10 minutes. Stop
unit and check oil level. If level is still low, add oil only after
determining that piping system is designed for proper oil re-
turn and that system is not leaking oil.
Refrigerant Service Ports —
service ports: one on the suction line, one on the liquid line,
and one on the compressor discharge line. Be sure caps on
the ports are tight.
Sequence of Operation —
to unit, the transformer (TRAN) is energized. The crankcase
heater is also energized.
COOLING — With the thermostat subbase in the cooling
position, and when the space temperature comes within
2° F (1° C) of the cooling set point, the thermostat makes
circuit R-O. This energizes the reversing valve solenoid (RVS)
and places the unit in standby condition for cooling.
As the space temperature continues to rise, the second stage
of the thermostat makes, closing circuit R-Y. When com-
pressor time delay (5 ± 2 minutes) is completed, a circuit is
made to contactor (C ), starting the compressor (COMP) and
outdoor-fan motor (OFM). Circuit R-G is made at the same
time, energizing the indoor-fan contactor (IFC) and starting
the indoor-fan motor (IFM) after one-second delay.
When the thermostat is satisfied, contacts open, deener-
gizing C. The COMP, IFM, and OFM stop.
HEATING — On a call for heat, thermostat makes circuits
R-Y and R-G. When compressor time delay (5 ± 2 minutes)
is completed, a circuit is made to C, starting COMP and OFM.
Circuit R-G also energizes IFC and starts IFM after a 1-second
delay.
10
Each unit system has 3
When power is supplied

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents