Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48EJ Installation And Service Instructions Manual page 20

Single package rooftop units electric cooling/gas heating
Hide thumbs Also See for SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48EJ:
Table of Contents

Advertisement

VOLTAGE
UNIT
NOMINAL
RANGE
SIZE
VOLTAGE
Min Max RLA LRA RLA LRA Qty Hp FLA
48E
(3 Ph 60 Hz)
208/230
187
254
044
460
414
508
575
518
632
208/230
187
254
048
460
414
508
575
518
632
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and
Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Table 4 — Electrical Data (cont)
COMPRESSOR
No. 1
No. 2
69.2
345
69.2
345
4
28.8
173
28.8
173
4
26.7
120
26.7
120
4
82.1
446
69.2
345
4
42.3
223
28.8
173
4
34.6
164
26.7
120
4
or
POWER
OFM
IFM
EXHAUST
(ea) Hp FLA FLA LRA
15 46.2/
42.0
23.6 41.6
20 59.4/
1
5.3
54.0
23.6 41.6
25 74.8/
68.0
23.6 41.6
15
21.0
12.6 23.6
1
2.7
20
27.0
12.6 23.6
25
34.0
12.6 23.6
15
17.0
12.6 23.6
1
2.4
20
22.0
12.6 23.6
25
27.0
12.6 23.6
20 59.4/
54.0
23.6 41.6
74.8/
1
5.3
25
68.0
23.6 41.6
30 88.0/
80.0
23.6 41.6
20
27.0
12.6 23.6
1
2.7
25
34.0
12.6 23.6
30
40.0
12.6 23.6
20
22.0
12.6 23.6
1
2.4
25
27.0
12.6 23.6
30
32.0
12.6 23.6
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
20
COMBUSTION
POWER SUPPLY
FAN MOTOR
FLA
MCA
0.96
223.1/218.9 275/275
0.96
246.7/242.5 300/300
0.96
236.3/230.9 300/300
0.96
259.9/254.5 300/300
0.96
251.7/244.9 300/300
0.96
275.3/268.5 300/300
0.50
96.6
0.50
109.2
0.50
102.6
0.50
115.2
0.50
109.6
0.50
122.2
0.50
86.7
0.50
99.3
0.50
91.7
0.50
104.3
0.50
96.7
0.50
109.3
0.96
252.4/247.0 300/300
0.96
276.0/270.6 300/300
0.96
267.8/261.0 300/300
0.96
291.4/284.6 300/300
0.96
281.0/273.0 300/300
0.96
304.6/296.6 350/300
0.50
119.5
0.50
132.1
0.50
126.5
0.50
139.1
0.50
132.5
0.50
145.1
0.50
101.6
0.50
114.2
0.50
106.6
0.50
119.2
0.50
111.6
0.50
124.2
452 + 464 + 455
3
1371
=
3
= 457
7
457
= 1.53%
MOCP*
125
125
125
125
125
150
110
125
110
125
110
125
150
150
150
175
150
175
125
125
125
150
125
150

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents