CD Automation REVO C 2PH User Manual

CD Automation REVO C 2PH User Manual

From 30a to 40a
Hide thumbs Also See for REVO C 2PH:
Table of Contents

Advertisement

Quick Links

USER'S MANUAL
Rev. 02/2022
016
CD Automation S.r.l.
Via Picasso, 34/36 - 20025 Legnano (MI)- Italy
Tel. +39 0331 577479 - Fax +39 0331 579479
E-mail: info@cdautomation.com - Web: www.cdautomation.com
2PH
from 30A to 40A
M-RC2-30-40

Advertisement

Table of Contents
loading

Summary of Contents for CD Automation REVO C 2PH

  • Page 1 USER’S MANUAL Rev. 02/2022 from 30A to 40A M-RC2-30-40 CD Automation S.r.l. Via Picasso, 34/36 - 20025 Legnano (MI)- Italy Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com...
  • Page 3: Declaration Of Conformity

    P.I. 08925720156 -Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com Declare that the product / Dichiara che il prodotto: Revo C 2Ph 30-40A PRODUCT DESCRIPTION: Electric power control SCOPE OF APPLICATION: Thermal control process DESCRIZIONE DEL PRODOTTO: Unità...
  • Page 4: Important Warnings For Safety

    User’s manual REVO C 2PH from 30A to 40A Important warnings for safety This chapter contains important information for the safety. The not observance of these instructions may result in serious personal injury or death and can cause serious damages to the Thyristor unit and to the components system included.
  • Page 5 User’s manual REVO C 2PH from 30A to 40A WARNING! All service including inspection, installation, wiring, maintenance, troubleshooting, fuse or other user serviceable component replacement must be performed only by properly qualified personnel. Service personnel must read this manual before proceeding with work. While service is being performed unqualified personnel should not work on the unit or be allowed in the immediate vicinity.
  • Page 6 User’s manual REVO C 2PH from 30A to 40A AVERTISSEMENT! Au moment de relever des mesures de tension ou de courant en direct, utiliser un équipement de protection individuelle approprié pour les tensions et les potentiels d’arc électrique concernés. WARNING! Verify the voltage and current ratings of the power controller are correct for the application. AVERTISSEMENT! Vérifier que les valeurs de tension et de courant du régulateur de puissance sont correctes pour l’application.
  • Page 7: Maintenance

    User’s manual REVO C 2PH from 30A to 40A Maintenance In order to have a corrected cooling, the user must clean the heat-sink and the protective grill of the fans. The frequency of this servicing depends on environmental pollution. Also check periodically if the screw for the power cables and safety earth are tightened correctly (See Connection Diagram).
  • Page 8: Table Of Contents

    User’s manual REVO C 2PH from 30A to 40A Summary Declaration of conformity......3 Important warnings for safety .
  • Page 9 User’s manual REVO C 2PH from 30A to 40A 10.5 Using the Configurator ........48 10.6 Software General information .
  • Page 10: Introduction

    User’s manual REVO C 2PH from 30A to 40A Introduction A thyristor unit is semiconductor device which acts as a switch formed by two thyristors in antiparallel. To switch on the alternating current the input signal will be on and the thyristor will switch off at first Zero Crossing voltage with no input signal.
  • Page 11: Advantages Compared With Analog Thyristor Unit

    User’s manual REVO C 2PH from 30A to 40A Advantages compared with analog thyristor unit Communication RS485 is a standard feature of REVO C this allows the use of many information like: current, power, load state and all the parameters for diagnostic and configuration. Ulterior advantages of the digital system vs the analogical is the flexibility and the possibility of implement special characteristics without chan- ge the hardware.
  • Page 12: Software Configurator

    User’s manual REVO C 2PH from 30A to 40A Software Configurator Thyristor configurator software is free and is possible download it from our site. If the Order Code is in line with requirement, then unit has been already configured in Factory and it’s ready to use.
  • Page 13: Quick Start

    User’s manual REVO C 2PH from 30A to 40A Quick Start Attention: this procedure must be carried out by skilled people only. If your REVO C code is in line with what you really need, then the main configuration is already done by Producer and you just need to do the following steps: Verify REVO C current sizing.
  • Page 14: Basic Connections And Sizing

    User’s manual REVO C 2PH from 30A to 40A Basic Connections and sizing Star wiring with resistive load (control on two phases with REVO C-2PH) I= P 1,73V V = Nominal voltage of the load I = Nominal current of the load P = Nominal power of the load Delta wiring with resistive load (control on two phases with REVO C-2PH) I= P...
  • Page 15: Identification And Order Code

    User’s manual REVO C 2PH from 30A to 40A Identification and Order Code 5.1 Identification of the unit Caution: Before to install, make sure that the Thyristor unit have not damages. If the product has a fault, please contact the dealer from which you purchased the product. The identification label give all the information regarding the factory settings of the Thyristor unit, this label is on the unit, like represented in figure.
  • Page 16: Order Code

    Option that allows communication with a smart phone. From your WiFi smart phone via the CD Automation App, direct to your thyristor unit in the cabinet to read current, voltage, power and energy totalization as well as the ability to change parameters to improve process and product quality without opening the cabinet door.
  • Page 17: Technical Specifications

    User’s manual REVO C 2PH from 30A to 40A Technical Specifications 6.1 General features Cover and Socket material: PolymericV2 Mounting: DIN bar (thickness type 1mm Max) Utilization Category: AC-51 AC-55b IP Code: Method of Connecting: Load in Delta, Load in Star Auxiliary voltage, power supply Control Circuit: TR1 range 1 = 90:135V (8 VA Max) (10 VA Max)
  • Page 18: Environmental Installation Conditions

    User’s manual REVO C 2PH from 30A to 40A 6.4 Environmental installation conditions Ambient temperature 0-40°C (32-104°F) at nominal current. Over 40°C-104°F use the derating curve (max 50°C). Storage temperature -25°C to 70°C -13°F to 158°F Installation place Don’t install at direct sun light, where there are conductive dust, corrosive gas, vibration or water and also in salty environmental.
  • Page 19: Wi-Fi Transmitter Module

    User’s manual REVO C 2PH from 30A to 40A 6.7 Wi-Fi Transmitter Module Models RC_ _ _-_ _ _ _ _-_ _ _ with WiFi option contains a Wi-Fi transmitter module, see model label plate for details on which module is installed. The transmitter module is mounted on the top of the microprocessor board.
  • Page 20: Installation

    User’s manual REVO C 2PH from 30A to 40A Installation Before to install, make sure that the Thyristor unit have not AIR FLOW OUT (V) damages. If the product has a fault, please contact the dealer from which you purchased the product. Verify that the product is the same thing as ordered.
  • Page 21: Dimensions And Weight

    User’s manual REVO C 2PH from 30A to 40A 7.1 Dimensions and weight REVO C 2PH Size: SR10 (2PH) Size: SR10 W (mm): H (mm): D (mm): Weight (Kg): 1,76 7.2 Fixing holes 24,5 5,25 11,5 11,5...
  • Page 22: Wiring Instructions

    User’s manual REVO C 2PH from 30A to 40A Wiring instructions The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply, for this reason in accord to the fundamental practices rules is opportune take some precautions: •...
  • Page 23: Access To L1-L3 And T1-T3 Terminal Screw

    User’s manual REVO C 2PH from 30A to 40A 8.1 Access to L1-L3 and T1-T3 terminal Screw 1. Open fuse holder by pulling the frontal cover 2. Fix the wire on Ln 3. Fix the wire on Tn 4. Close the cover by pressing Repeat for each Phase...
  • Page 24 User’s manual REVO C 2PH from 30A to 40A Locations of the line power, load, earth ground and control signal connections. Cover closed Cover tipped forward Iout 0.0A Ref. 0.0%...
  • Page 25: Command Terminals

    User’s manual REVO C 2PH from 30A to 40A 8.2 Command Terminals Warning: Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources. 8.2.1 Terminal block M2 Terminal Description COM I - Common Digital Input DI 2 –...
  • Page 26: Schematic

    User’s manual REVO C 2PH from 30A to 40A 8.2.5 Terminal block M6 Terminal Description Auxiliary +24Vdc 500mA Input backup power supply for communication - Analog Input2 (0-10Vdc/4-20mA Analog Setpoint) – 0 Volt + Analog Input2 (0-10Vdc/4-20mA Analog Setpoint) Retransmission Output 0-10Vdc 4-20mA 8.2.1 Terminal block M5 (only with Second serial485 optional) Terminal Description...
  • Page 27 User’s manual REVO C 2PH from 30A to 40A Caution: this procedure must be performed only by qualified persons Indicative connection diagrams. Refer to local regulations for proper system protection. Option Second Ethernet Profibus Branch Circuit Serial RS485 Protection Fuse 1A Max MICRO USB 2.0 Function:...
  • Page 28 User’s manual REVO C 2PH from 30A to 40A Top View Down View 8.3.1 SSR Control Input schematic For SSR input use follow the schematic below and configure Digital Input 1 as Fast Enable. Analog Input 1 Entrée Analogique 1 INPUT INPUT * SSR Input: 4÷30Vdc 5mA Max (ON >4Vdc / OFF <1Vdc)
  • Page 29: Connection Diagram For 3 Phases (Control On 2 Phases)

    User’s manual REVO C 2PH from 30A to 40A 8.4 Connection Diagram for 3 phases (control on 2 phases) Caution: this procedure must be performed only by qualified persons. +24V IN Analog Voltage Input 2 Supply See order Retrans OUT code for the value Alarm Relay...
  • Page 30: Control Panel

    User’s manual REVO C 2PH from 30A to 40A Control Panel The Control Panel is placed on the front of the thyristor unit, on his display you can visualize the alarms, the input and output signals and all the configuration parameters. Iout0.0A Vout0.0V Pout0%...
  • Page 31: Menu Navigation

    User’s manual REVO C 2PH from 30A to 40A 9.1 Menu navigation The menus are accessible using the control panel keypad and display. Choose Enter Choose Edit HOME PAGE Menu Password Parameter Parameter Iout0.0A Password Set Point Iout0.0A 100% SP 100% Iout0.0A Set Point Menu...
  • Page 32: Control Panel Led

    User’s manual REVO C 2PH from 30A to 40A 9.2 Control Panel Led The four indicators on the control panel show the general state of the power controller. Flashing Power output set locally or via communications Local/Remote Power output set remotely (via analog input) Aux High Output enabled SP 100%...
  • Page 33: Parameter List

    User’s manual REVO C 2PH from 30A to 40A 9.4 Parameter list This chapter describes the parameter on the menus accessed via the control panel and Configurator softwa- re. To learn how to access the menus described below see “Menu navigation” chapter. Menu Listing The table below lists the parameters found on each menu.
  • Page 34 User’s manual REVO C 2PH from 30A to 40A 9.4.1 Operator Menu This section describes each item on the operator menu. Use this menu to view the measured values and basic settings of the power controller. The password to access this menu is 0. Modbus Par.
  • Page 35 User’s manual REVO C 2PH from 30A to 40A 9.4.2 Setup Menu This section describes each item on the setup menu. Use this menu to configure the power controller for the load. The password to access this menu is 2. Modbus Par.
  • Page 36 User’s manual REVO C 2PH from 30A to 40A 9.4.3 Advanced Setup Menu This section describes each item on the advanced setup menu. Use this menu to configure the power switching, closed loop control of power and adjustable settings for data logging and heater bakeout. The password to access this menu is 10.
  • Page 37 User’s manual REVO C 2PH from 30A to 40A Modbus Par. Parameter Name Description Default Range Unit Address Type Set the gain for the main loop. A larger Pb Power Read value yields a larger adjustment for a 0 to 255 Write given deviation Set how aggressively the integral part...
  • Page 38 User’s manual REVO C 2PH from 30A to 40A 9.4.4 Hardware Menu This section describes each item on the hardware menu. Use this menu to configure how the inputs and outputs are used in the application. The password to access this menu is 5. Modbus Par.
  • Page 39 User’s manual REVO C 2PH from 30A to 40A Modbus Par. Parameter Name Description Default Address Type DI1 Functn Choose how the signal detected by digital input 1 Read is used Write Option Description Value Enable Enable power output V Feedback Use voltage feed-back when on Local / Rmt Local when on / Remote when off...
  • Page 40 User’s manual REVO C 2PH from 30A to 40A Modbus Par. Parameter Name Description Default Address Type Choose for which conditions the digital output Alm Out Fn indicates alarm. The output always indicate an alarm when the heat sink is over temperature. The digital output is energized for normal operating condition and de-energized when the power Read...
  • Page 41 User’s manual REVO C 2PH from 30A to 40A Modbus Par. Parameter Name Description Default Range Unit Address Type value retransmitted Rtx Scale parameter to be represented by Read 0 to 9999 the full scale of the analog output. Write See the table below Recommended Resulting Signal...
  • Page 42 User’s manual REVO C 2PH from 30A to 40A 9.4.5 Communication Menu This section describes each item on the communication menu. Use this menu to configure the communication options. The password to access this menu is 3. Modbus Par. Parameter Name Description Default Address...
  • Page 43 User’s manual REVO C 2PH from 30A to 40A Modbus Par. Parameter Name Description Default Range Unit Address Type Set the amount of time to wait for WD Reset Read communication message before 0 to 255 Write triggering the watchdog error Wi-Fi Addr Indicate the IP address of the WiFi 94-95...
  • Page 44 User’s manual REVO C 2PH from 30A to 40A 9.4.6 Monitoring Menu This section describes each item on the monitoring menu. Use this menu to view the states of digital input, values of analog input and information about the power controller such as serial number and software version. The password to access this menu is 0.
  • Page 45 User’s manual REVO C 2PH from 30A to 40A Modbus Par. Parameter Name Description Range Unit Address Type Analog In1 Indicates the percent of full scale measured Read 0 to 100.0 by analog input 1 Only Analog In2 Indicates the percent of full scale measured Read 0 to 100.0 by analog input 2...
  • Page 46: Using The Configurator

    User’s manual REVO C 2PH from 30A to 40A Using the Configurator Confi gurator software can be used like an alternative of the power controller’s keypad and set the advanced features not available via the power controller’s onboard user interface. Here we explain how to use it.
  • Page 47 RS485 port so a USB-to-485 converter is required. 3) Launch the Confi gurator software an select REVO C: for single phase REVO C 2PH: for 2 phase power controller REVO C 3PH: for 3 phase power controller...
  • Page 48: Using The Configurator

    User’s manual REVO C 2PH from 30A to 40A 10.5 Using the Confi gurator After software has been installed, communication has been set up and model type selected, is possible operate with power controller. 10.5.1 To view or save a power controller’s settings using “Simple”...
  • Page 49 User’s manual REVO C 2PH from 30A to 40A 10.5.3 To download a recipe fi le into a power controller: 1) Click Simple, if not already on the Simple view 2) Click existing recipe Open 3) Locate and select the recipe fi le and click Open 4) Click 5) Click...
  • Page 50 User’s manual REVO C 2PH from 30A to 40A 10.5.8 To reset the power totals: 1) Click Test, if not already on the test view 2) Click Online 3) Click Reset Totals 4) Click 10.5.9 Setting Up and Using Data Logging To set up data logging: 1) Click Test, if not already on the test view 2) Click...
  • Page 51: Software General Information

    User’s manual REVO C 2PH from 30A to 40A 10.5.10 To retrieve a data log fi le from the power controller: 1) Click Test, if not already on the test view 2) Click Online 3) Click Load Analyzer 4) Click Connect 5) Select a fi le from the list 6) Click...
  • Page 52 User’s manual REVO C 2PH from 30A to 40A 10.6.2 Simple Section This section is used to create, save, upload and download recipes of parameters settings. Can be used also to see the settings in a controller. Simple page is the default page when select the model using the Model Button, but If not selected is possible access it clicking the Simple tab below the main menu.
  • Page 53 User’s manual REVO C 2PH from 30A to 40A 10.6.3 Test Section This section is used to monitor and adjust the operation of the power controller in real time using RS485 or USB communication port. After select the model, is possible access to this section clicking the “TEST”...
  • Page 54 User’s manual REVO C 2PH from 30A to 40A Buttons setup options: Firing: view and set the fi ring type and the associated parameters Feedback: view and set feedback type Communication: view and set communication options for ports, protocols and fi eldbus Confi gure and monitor the analog inputs: 1: click Ai 1 to view the signal type Analog Input...
  • Page 55 User’s manual REVO C 2PH from 30A to 40A 10.6.4. Load Analyzer Load Analyzer is used for monitoring values graphically represent Click on Load Analyzer button on the test page will open Load Analyzer window. Is possible see 3 channels (Ch 1, Ch 2 and Ch 3). For each channel confi gure a pen on the graph: On/Off...
  • Page 56 User’s manual REVO C 2PH from 30A to 40A 10.6.5 Data Log Window In the power controller the data log window is used to manage fi les and set up logging parameter like log interval time and date/time in rtc slider: Enable and disable data logging function.
  • Page 57 User’s manual REVO C 2PH from 30A to 40A 10.6.7 MSG view Message view display the communication activity between the computer and the power controller. PORT COM: use this view to see when the COM port is accessed and its settings MODBUS: Modbus communication protocol area Area: use this view to see parameters READ...
  • Page 58: Configurable Inputs And Outputs

    User’s manual REVO C 2PH from 30A to 40A Configurable Inputs and Outputs The REVO C power controller features two digital inputs, up to two analog inputs and a relay output. Some models also include an analog output for retransmitting a measured value to other automation equipment. This section describes the various functions of these inputs and outputs and how they interact with other features of the power controller.
  • Page 59: Analog Input 2: Set Point Or Feedback

    User’s manual REVO C 2PH from 30A to 40A 11.3 Analog Input 2: Set Point or Feedback What this input does is user-configurable. Connect an analog signal that indicates: • An alternate set point signal • Measured power, voltage or current from an external device used as feedback. This input accepts current, voltage and potentiometer signals.
  • Page 60: Alarm Description

    User’s manual REVO C 2PH from 30A to 40A Alarm description 12.1 Heater Break Alarm This option allows you to diagnose any load breakage. The diagnostics is based on the comparison of the value of the nominal resistance of the load with respect to the resistance measured in real time. The nominal resistance is calculated using the Operative Load Voltage (Nom Line V) and Nominal Current of the load (Nominal I) parameters.
  • Page 61: Aux High

    User’s manual REVO C 2PH from 30A to 40A 12.2. AUX High This alarm is displayed when the auxiliary supply voltage exceeds the established ranges. If the alarm situation persists for more than 5 seconds, the unit will go into protection. 12.3 AUX Low This alarm is displayed when the auxiliary supply voltage is lower than the established ranges.
  • Page 62: 13 "Enable" Function In Static Unit

    User’s manual REVO C 2PH from 30A to 40A “Enable” Function in static Unit The “Enable” function can work in several ways • from Digital input • from Serial Port • from Digital Input + Serial Port • from FieldBus •...
  • Page 63: Using Serial Port Rs485 Only

    User’s manual REVO C 2PH from 30A to 40A 13.2 Using Serial Port RS485 only The static unit has an RS485 Modbus RTU serial port always present. By setting the Digital Input as “Not Used” or different from “Enable” it is possible to control the enable from serial port with bit 2 of parameter 14 If bit 2 = 1: Enabled If bit 2 = 0: Disabled...
  • Page 64: Using Fieldbus Only

    User’s manual REVO C 2PH from 30A to 40A 13.4 Using FieldBus only The static unit as an option can be ordered with a FieldBus (Ex: profinet). This option continuously writes the values on the unit keeping them up to date. Using the field bus it is possible to change the status of the Sw contact with bit 2 of the “Command table”...
  • Page 65: Using Digital Input + Fieldbus

    User’s manual REVO C 2PH from 30A to 40A 13.5 Using Digital Input + FieldBus The static unit as an option can be ordered with a FieldBus (Ex: profinet). This option continuously writes the values on the unit keeping them up to date. The external contact Sw and the internal software contact Sw are connected in series, therefore if you want...
  • Page 66: Firing Type

    User’s manual REVO C 2PH from 30A to 40A Firing type Choose a correct firing type allows to optimize the thyristor unit for the installed load. The firing type has already configured in line with customer requirements that are defined in the Order Code. The Order Code is written on the identification label.
  • Page 67: Control Mode (Feed-Back)

    User’s manual REVO C 2PH from 30A to 40A Control Mode (feed-back) The Control Mode (feed-back) type has already configured in line with customer requirements that are defined in the Order Code. The Order Code is written on the identification label. However, if you wish to change the Control Mode (feed-back) type you can use the software configurator or the Control Panel.
  • Page 68: Electronic Boards

    User’s manual REVO C 2PH from 30A to 40A Electronic boards 16.1 How to access...
  • Page 69: Supply The Electronic Board

    User’s manual REVO C 2PH from 30A to 40A 16.2 Supply the Electronic Board The REVO C thyristor unit, to work, requires a voltage supply for the electronic boards. The Max consumption is 10VA. The voltage supply for the electronic boards is configured in line with customer requirements that are defined in the Order Code.
  • Page 70: 24Vdc Input Auxiliary Supplemental Power

    User’s manual REVO C 2PH from 30A to 40A 24Vdc input Auxiliary supplemental power The 24Vdc Auxiliary Supply input in Terminal Block M6, terminals 17 and 18, can be used as an auxiliary power supply when the main network fails. This auxiliary power supply keeps the communication circuits powered allowing data to be transferred to the supervision system.
  • Page 71: Rs485 Serial Port

    User’s manual REVO C 2PH from 30A to 40A RS485 Serial port Down M3 Terminal Description RS485 A+ RS485 B- The serial communication port RS485 is available on the Command Terminals. On this port may be done a network up to 127 REVO C. Fieldbus communication option Other serial communication port are available as option, see Communication Manual for details.
  • Page 72: Internal Fuse

    User’s manual REVO C 2PH from 30A to 40A Internal Fuse The thyristor unit have internal fuse extrarapid at low I T for the thyristor protection of against the short-circuits. The Fuses must have I T 20% less than thyristor’s I T.
  • Page 73 CD Automation S.r.l. Via Picasso, 34/36 - 20025 Legnano (MI)- Italy Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com...

This manual is also suitable for:

M-rc2-30-40

Table of Contents