→Table 7—Model 58ZAV Orifice Size† and Manifold Pressure for Correct Input
(Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 percent per 1000 Ft Above Sea Level)*
AVG GAS
ALTITUDE
HEAT VALUE
RANGE
AT ALTITUDE
(FT)
(BTU/CU FT)
700
725
750
775
5001
800
825
to
850
875
6000
900
925
950
975
1000
AVG GAS
ALTITUDE
HEAT VALUE
RANGE
AT ALTITUDE
(FT)
(BTU/CU FT)
650
675
700
6001
725
750
to
775
800
7000
825
850
875
AVG GAS
ALTITUDE
HEAT VALUE
RANGE
AT ALTITUDE
(FT)
(BTU/CU FT)
625
650
675
7001
700
725
to
750
775
8000
800
825
850
AVG GAS
ALTITUDE
HEAT VALUE
RANGE
AT ALTITUDE
(FT)
(BTU/CU FT)
600
625
8001
650
675
to
700
725
9000
750
775
800
* For size 135-20 only, input is 22,500 Btuh per burner. Deduct 0.1-in. wc from manifold pressure shown in table. Change orifice size if manifold pressure falls below
3.2-in. wc on altitudes up to 2000 ft, otherwise change orifice size if manifold pressure falls below 2.0-in. wc.
† Orifice sizes shown in BOLD are factory installed.