Manual – using a manual activation switch - FP-14053 switch. c. Combination – which will allow automatic via the LHD or manual from the switch. Power Supply – designed to operate on 6 to 30vDC supply. Number of FirePro units will depend on incoming power supply.
FirePro units have a self-activation temperature of 300⁰C. Placement of units should be carefully selected. All cabling in the FirePro Installation MUST be Installed using min 0.75mm shielded Fire Rated Cable Power MUST be connected directly power supply OR Battery to ensure operation of the system.
Rev 3.1 Servicing & Maintenance The FirePro Suppression system should be serviced at least every 6 months in accordance with AS 1851, more often in aggressive environments. Periodic visual inspections of the installed system must also be conducted by the operators to ensure all installed parts are free from debris, rust, or electrical faults.
Firepro units shall be securely installed. Use heavy duty brackets where necessary. Brackets should be capable of handling the risk evironment, including vibration. Firepro units must be installed at NOT less than the minimum safe distances as specified in the design calcuations.
FirePro generators must remain disconnected until system is completed and fire control panel is no longer in a fault or alarm condition. The FirePro Universal Test Module (P/N FP-08800) can be used to take the panel out of a fault condition.
This is an EXTRACT ONLY from the full SDS. The SDS is prepared by Chemwatch - to view the full www.chemwatch.com.au SDS go to HAZARDOUS SUBSTANCE. DANGEROUS GOODS. According to NOHSC Criteria, and ADG Code. PRODUCT NAME CELANOVA FIREPRO PRODUCT USE Fire extinguishing agent.