API 1000 G Quick Start Manual

API 1000 G Quick Start Manual

Dc input alarm trips, factory ranged

Advertisement

Quick Links

DC Input Alarm Trips, Factory Ranged

0-100 mV to 300 VDC, 0-1 mA to 0-900 mADC
Output:
One 8 Amp DPDT Relay or Two 8 Amp SPDT Relays
O Field Adjustable Setpoints
O Plug-In Design for Fast Installation
O Input LoopTracker
and Alarm Status LEDs
®
O Alarm Test, Optional Reset Button
O Sinking mA Input

Applications

Q Process Limit Backup Alarm
Q Tank Level Alarm
Q Process Signal Over, Under, Out-of-Range Alarm
DC Input Range
Factory configured, please specify input type and range
System voltages should not exceed socket voltage rating
Voltage:
0-100 mVDC
to
0-300 VDC
Current:
0-1 mADC
to
0-900 mADC
Input Impedance and Burden
Voltage:
250 kΩ minimum
50 Ω typical
Current:
Voltage burden: 1.25 VDC at 20 mA current input
Isolation and Input Protection
750 VAC
or 750 VDC common mode protection
p
Input isolated from power supply
LoopTracker
Variable brightness LED indicates input loop level and status
API 1000 G Relay Output
Two SPDT form C contact sets operating in unison as one
DPDT contact set
One setpoint, 12 turn potentiometer, 0-100% of span
Factory configured alarm type
Normal acting alarm
Standard: HI alarm
Optional: LO alarm
API 1020 G Relay Output
Two independent SPDT form C contact sets
Two setpoints, two 12 turn potentiometers, 0-100% of span
Normal acting alarms
Standard: HI/LO alarm
Options: LO/LO, HI/HI, LO/HI alarms
Internal jumpers for HI/LO, LO/LO, HI/HI, LO/HI
Relay Contact Rating
8 A @ 240 VAC resistive load or 30 VDC resistive load
5 A @ 240 VAC inductive load (cos f = 0.4)
3.5 A @ 30 VDC inductive load (L/R = 7ms)
See graph on other side for relay load ratings
Caution: Do not exceed socket voltage rating
Use an RC snubber for inductive loads
Alarm trip/reset window is symmetrical about the setpoint
API 1000 G
1.0 to 100% of span, 12 turn potentiometer.
API 1020 G
Fixed at 1% of span, standard
API 1020 G A Adjustable deadbands, 1.0 to 100% of span,
1 turn potentiometer for each setpoint
Output Test Button
Toggles relay(s) to opposite state when pressed
Response Time
70 milliseconds typical
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than ±0.02% of span per °C stability, calculated not
tested
Housing and Sockets
IP 40, requires installation in panel or enclosure
API 011 or API 011 FS socket
Socket mounts to 35 mm DIN rail or can be surface mounted
Power
Standard:
115 VAC ±10%, 50/60 Hz, 2.5 W max.
P option:
85-265 VAC 50/60 Hz, 60-300 VDC, 2.5 W typ.
A230 option: 230 VAC ±10%, 50/60 Hz, 2.5 W max.
D option:
9-30 VDC, 2.5 W typical
A
A
P
P
BSOLUTE
BSOLUTE
ROCESS
ROCESS
Variable Brightness Input LED
Bi-Color Relay LED
Deadband Adjustment
Setpoint Adjustment
Output Test Button
API 1000 G
A Option Deadband Adjustments
Variable Brightness Input LED
Bi-Color Relay 2 LED
Bi-Color Relay 1 LED
Setpoint 2 Adjustment
Setpoint 1 Adjustment
Output Test Button
API 1020 G

Description

The API 1000 G and API 1020 G are factory configured for
either a DC voltage or current input and provide alarm contact
outputs. Heavy duty relay contacts allow the module to directly
control high capacity loads.
The API 1000 G provides a single setpoint adjustment and
DPDT relay contacts. The normal acting alarm output can
be factory configured for HI or LO operation. Top-accessible
potentiometers are used to adjust the alarm setpoint and
deadband.
The API 1020 G contains two independent setpoints with
two SPDT relay contact outputs. The normal acting alarm
output can be factory configured for HI/HI, HI/LO, LO/HI or
LO/LO operation. Top-accessible potentiometers are used to
adjust each alarm setpoint. Deadband is fixed at 1% of span.
Adjustable deadbands are optional.
Model
Input
API 1000 G
API 1000 G A230
Factory ranged, specify
API 1000 G P
mV, V, or mA range
API 1000 G D
API 1020 G
API 1020 G A230
Factory ranged, specify
mV, V, or mA range
API 1020 G P
API 1020 G D
Options—add to end of model number
L
1000 G with LO trip. Alarm trips on decreasing signal.
HH 1020 G with HI/HI trip. Alarms trip at their respective
trip points on increasing signal.
LL
1020 G with LO/LO trip. Alarms trip at their respective
trip points on decreasing signal.
LH 1020 G with LO/HI trip instead of HI/LO.
A
1020 G with adjustable deadbands.
U
Conformal coating for moisture resistance
I
I
NSTRUMENTS
NSTRUMENTS
API 1000 G, API 1020 G
2.38"
1.75"
2.38"
api-usa.com/1000
1.75"

LoopTracker and Alarm Status LEDs

API exclusive features include a LoopTracker LED that varies in
intensity with changes in the process input signal.
A red/green bi-color alarm status LED (two on the API 1020
G) visually indicate alarm status. These LEDs provide a quick
visual picture of your process at all times.

Output Test

API's exclusive functional test button can be used to verify the
alarm and system operation. Press the Test button to toggle
the alarm relay(s) to the opposite state. The output test but-
ton greatly aids in saving time during initial startup and/or
troubleshooting.
Standard Alarm Configuration
Single setpoint one DPDT relay
HI alarm, normal acting
2 setpoints, 2 SPDT relays
HI/LO alarms, normal acting
Accessories—order as a separate line item
API 011
API 011 FS 11-pin finger safe socket, DIN rail or surface mount
API CLP1
API 011 FS
300 V Rating
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
Fax: 800-949-7502
2.75"
Hot Swappable
Plug-In Design
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
Free Factory
Quick Link
I/O Setup!
Power
115 VAC
230 VAC
85-265 VAC or 60-300 VDC
9-30 VDC
115 VAC
230 VAC
85-265 VAC or 60-300 VDC
9-30 VDC
11-pin socket, DIN rail or surface mount
Module hold-down spring for high vibration or
mobile applications
API 011
API CLP1
300 V Rating
api-usa.com
©
09-21

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 1000 G and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for API 1000 G

  • Page 1 Description LoopTracker and Alarm Status LEDs Factory configured alarm type The API 1000 G and API 1020 G are factory configured for API exclusive features include a LoopTracker LED that varies in Normal acting alarm either a DC voltage or current input and provide alarm contact intensity with changes in the process input signal.
  • Page 2 Setpoint 2 = HI from 1 to 100% of the span. (Standard) No Alarm HI Alarm LO Alarm The deadband is fixed at 1% of span on the API 1020 G. The API GREEN Relay 1 Relay 1 GREEN Relay 1...

This manual is also suitable for:

1000 g a2301000 g p1000 g d1020 g1020 g a2301020 g p ... Show all

Table of Contents