API APD 1700 Installation And Setup

API APD 1700 Installation And Setup

Frequency input alarm trips, factory ranged input

Advertisement

Quick Links

Frequency Input Alarm Trips, Factory Ranged Input
0-25 Hz to 0-20 kHz

Output:

Two 8 Amp SPDT Relays
O Factory Set Frequency Input Range
O Adjustable Setpoint and Deadband Potentiometers
O Input LoopTracker
and Alarm Status LEDs
®
O Full 1200 V Isolation
O Alarm Test, Optional Reset Button

Applications

Q Machinery Speed Alarm
Q Redundant or Backup Alarm
Q Conveyor or Machine Malfunction Alarm

Frequency Input Range

Factory configured, please specify input type and range
Frequency:
0-25 Hz to 0-20 kHz
Sine wave, sawtooth, or square wave with min. 5 µsec pulse
Input Impedance
At maximum sensitivity:
10 kW nominal
At minimum sensitivity:
100 kW nominal
Input Sensitivity/Hysteresis
Multi-turn potentiometer for sensitivity adjustment
Maximum sensitivity:
±25 mV typical
Minimum sensitivity:
±2.5 V typical
Input Amplitude Range
100 mV to 150 V
RMS
Any waveform with minimum 100 mV amplitude change

Input Power Supply

15 VDC ±10%, regulated, 25 mADC, max. ripple, <10 mV
May be used to power sensor
Input Protection
Normal mode:
200% of input rating
Common mode:
600 VDC or 600 VAC p input to ground
LoopTracker
Variable brightness LED indicates input loop level and status

APD 1700 Relay Output

Dual SPDT Form C contact sets operating in unison
1 setpoint adjustment, 1 deadband adjustment
Standard: HI alarm, non-latching, normal acting
Options: LO alarm, latching, reverse acting
APD 1720 Relay Output
2 independent SPDT Form C contact sets
2 setpoint adjustments, 2 deadband adjustments
Factory configured alarm
Standard: HI/LO alarm, non-latching, normal acting
Options: LO/LO, HI/HI, LO/HI alarms, band alarms,
latching, reverse acting

Relay Contact Ratings

8 A max @ 240 VAC resistive load
External contact protection such as an RC snubber is recom-
mended for inductive loads
AC inductive load
AC resistive
(cos f = 0.4)
8
5
3
DC inductive load
1
(L/R = 7 ms)
0.5
DC resistive
0.3
load
0.1
0
3 5 10
30 50 100 300 500
Switching Voltage (V)

Setpoint

12 turn potentiometer adjustable from 0 to 100% of span

Deadband

12 turn potentiometer adjustable from 1 to 100% of span
Output Test/Reset Button
Front button or external contact closure toggles relays to
opposite state when pressed.
Resets relay if latching relay option is ordered.
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than 0.04% of span per °C
A
A
P
P
BSOLUTE
BSOLUTE
ROCESS
ROCESS
Removable Plugs
Alarm Test Function
Two 8 Amp SPDT
Alarm Relays
Input LoopTracker LED
Alarm Status LED
Adjustable Deadband
Adjustable Setpoint
Custom Input Ranges
Universal Power
RMS
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
Applications Link
api-usa.com/apps
Free Factory
I/O Setup!

Dimensions

0.89" W x 4.62" H x 4.81" D
(22.5 x 117 x 122 mm)
Height includes connectors
Housing and Connectors
IP 40, requires installation in panel or enclosure
For use in Pollution Degree 2 Environment
Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors, 14 AWG max wire size
load

Power

85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum
Model
APD 1700
APD 1700 D
APD 1720
APD 1720 D
Alarm Options—add to end of model number
L
APD 1700 with LO trip. Alarm trips on decreasing signal.
HH APD 1720 with HI/HI trip. Alarms trip at their respective
trip points on increasing signal.
LL APD 1720 with LO/LO trip. Alarms trip at their respective
trip points on decreasing signal.
LH APD 1720 with LO/HI trip. Alarm 1 trips on decreasing
signal. Alarm 2 trips on increasing signal.
BA APD 1720 with band alarm. Alarm trips if signal is
outside LO and HI trip points.
I
I
NSTRUMENTS
NSTRUMENTS
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
File E145968
85-265 VAC, 60-300 VDC
model only

Input

Standard Alarm Configuration
Single setpoint dual SPDT relays
Factory ranged
HI alarm, non-latching, normal acting
specify frequency range
0-25 Hz to 0-20 kHz
HI/LO alarms, non-latching, normal acting
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
APD 1700, APD 1720
Quick Link:
1 2 3 4
5 6
7 8
9 10 11 12
13 14 15 16

Description

The APD 1700 and APD 1720 accept a frequency input and
provides a visual alarm indication and alarm relay contact
outputs.
The input is factory configured to a specific frequency
input range. The input can be of any type as long as it has
a minimum of 100 mV amplitude change and a minimum 5
microsecond pulse width. Input sensitivity is potentiometer
adjustable.
Front-accessible potentiometers are used to adjust alarm
setpoint and deadband.
LoopTracker and Alarm Status LEDs
API exclusive features include a LoopTracker LED that varies
in intensity with changes in the process input signal.
A red/green bicolor alarm status LED (two on the APD 1720)
visually indicate alarm status. These LEDs provide a quick
visual picture of your process at all times.
Output Test / Unlatch
The API exclusive Output Test button can be used to verify the
alarm and system operation and also provides the additional
function of unlatching the alarm when the latching option has
been ordered. This feature can be remotely operated.
The output test button greatly aids in saving time during initial
startup and/or troubleshooting.
2 setpoints, 2 SPDT relays
IBA APD 1720 with inverse band alarm. Alarms trip if signal
is between LO and HI trip points.
HT Latching alarm with push button reset
HP Latching alarm with power-off reset. Module power
must be turned off to reset alarms
RA Reverse-acting alarms. Relay coils energized in an alarm
condition. No alarm condition with module power off.
U
Conformal coating for moisture resistance
Accessory—order as separate line item
API BP4 Spare removable 4 terminal plug, black
api-usa.com
Fax: 800-949-7502
api-usa.com/1700
See Wiring
Diagrams on
Next Page
Power
85-265 VAC or 60-300 VDC
9-30 VDC or 10-32 VAC
85-265 VAC or 60-300 VDC
9-30 VDC or 10-32 VAC
03-22
©

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the APD 1700 and is the answer not in the manual?

Questions and answers

Summary of Contents for API APD 1700

  • Page 1 Description Common mode: 600 VDC or 600 VAC p input to ground Made in USA The APD 1700 and APD 1720 accept a frequency input and LoopTracker File E145968 provides a visual alarm indication and alarm relay contact Variable brightness LED indicates input loop level and status 85-265 VAC, 60-300 VDC outputs.
  • Page 2 Cu 60/75°C the alarm, depending on the type of latching option. The alarm will Module Power The APD 1700 operates two sets of relays in unison with a single conductors only reset if the alarm condition no longer exists. setpoint. The dual SPDT contact sets are in a Form C configuration.

This manual is also suitable for:

Apd 1720Apd 1700 dApd 1720 d

Table of Contents