The compact design allows a simple integration even in constructions and machines with restricted space conditions. • Base elements of DMU 10 D are 2 piezoresistive stainless steel sensors. DMU 11 D is based on a piezoresistive silicon pressure sensor.
• For the connection of the pressure lines, a sealing has to be installed by the operator. • For the pipe assembly, an installation as zero-potential as possible must be observed. • Consider for the installation of a DMU 10 D, that the pressure ports must not be turned against the housing! 3.2 General installation steps...
Fig. 2 Mounting possibilities 3.3 Installation steps for DMU 10 D with G 1/8" internal thread • Check to ensure that the O-rings fit properly into the grooves. (O-rings are not included in the scope of delivery.) •...
Page 5
Please check if the delivered seal is placed between plug and cable socket. Fasten the cable socket on the device by using the screw, after connecting the cable. Pin configuration: DMU 10 D DMU 11 D Electrical connection ISO 4400...
4. Commissioning Please note that for starting up, the device has to be stressed by pressure simultaneously at both pressure ports. Otherwise the sensor could be damaged. For one-sided pressure admission, the permissible static pressure (one-sided) must be attended. Please take this out of the current data sheet.
1. Disconnect the product from mains. 2. Dismount the product (see chapter "Mounting", reverse sequence of steps). 3. Dispose of the product. 11. Warranty See our terms and conditions at www.afriso.com or your purchase contract for information on warranty.