Program The Display - Sentry 200 Owner's Manual

Liquid level gauge
Table of Contents

Advertisement

Sentry
LIQUID LEVEL GAUGE MODEL 200 or 200C
OWNER MANUAL
The display plug-in screw plug is labeled for relay 1-4
terminals. See Fig 3.6.1.
3.7. Program the display for the required alarm points and
control relay settings referring to the following
instructions and the programming mode menu
supplied separately.
3.7.1. To enter the programming mode hold the
ENTER and ESC buttons down for 5 seconds.
The display will move through the diagnostic
mode
of the menu, the HIGH LEVEL ALARM.
Scroll through the first level of menu items by
using the UP and DOWN buttons. Select the next
level of each menu item by pressing the ENTER
button. Move back to the previous level of menu
items by pressing the ESC button. Pressing ESC
will not change any values. Press ENTER to
temporarily store each change into memory. The
display will verify the temporary
when ENTER is pressed.
3.7.2. Program a HIGH LEVEL ALARM by setting the
trip point at the desired depth. As the water level
rises up past that depth, the red LED and the
audio alarm will activate. Set the release point
depth below the trip point to turn the alarm off as
the water level falls and returns to normal. A
release point set above the trip point will be
ignored but the alarm may "hunt". Set the audio
alarm on or off. If no HIGH LEVEL ALARM is
required, set the trip and release values higher
than the sensor length and the audio to off.
3.7.3. Program a LOW LEVEL ALARM by setting the
trip point at the desired depth. As the water level
falls below that depth the red LED and the audio
alarm will activate. Set the release point depth
above the trip point to turn the alarm off as the
water level rises and returns to normal. A release
point set below the trip point will be ignored but
and will then display the first item
status
REV 1.7
SEPT08
PAGE 6 OF 12