Allen-Bradley 6180P-12KSXP Installation Instructions Manual
Allen-Bradley 6180P-12KSXP Installation Instructions Manual

Allen-Bradley 6180P-12KSXP Installation Instructions Manual

Industrial integrated display computers with keypad

Advertisement

Quick Links

Installation Instructions
Industrial Integrated Display Computers
with Keypad
Catalog Numbers 6180P-12KSXP, 6180P-12BSXP, 6180P-12BPXP, 6180P-12BPXPDC,
6180P-12KPXP, 6180P-15KSXP, 6180P-15BSXP, 6180P-15BPXP, 6180P-15KPXP, 6180P-15BPXPDC
Topic
Before You Begin
Page
2
3
3
4
4
5
5
5
10
11
11
12
13
13
16
16
17
19

Advertisement

Table of Contents
loading

Summary of Contents for Allen-Bradley 6180P-12KSXP

  • Page 1: Table Of Contents

    Installation Instructions Industrial Integrated Display Computers with Keypad Catalog Numbers 6180P-12KSXP, 6180P-12BSXP, 6180P-12BPXP, 6180P-12BPXPDC, 6180P-12KPXP, 6180P-15KSXP, 6180P-15BSXP, 6180P-15BPXP, 6180P-15KPXP, 6180P-15BPXPDC Topic Page Important User Information Environment and Enclosure Information European Union Directive Compliance Installation Guidelines Operating Systems Before You Begin...
  • Page 2: Important User Information

    2 Industrial Integrated Display Computers with Keypad Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
  • Page 3: Environment And Enclosure Information

    Industrial Integrated Display Computers with Keypad 3 Environment and Enclosure Information Review the information on enclosures and environments before installing your computer. ATTENTION: This equipment is intended for use in a Pollution Degree 2 environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
  • Page 4: Installation Guidelines

    4 Industrial Integrated Display Computers with Keypad Installation Guidelines Follow these guidelines to make sure your product provides safe and reliable service. • The installation site must have sufficient power. • Make sure that sufficient space is available around air inlets and outlets to provide the circulation necessary for cooling.
  • Page 5: Before You Begin

    Industrial Integrated Display Computers with Keypad 5 Before You Begin Before unpacking the product, inspect the shipping carton for damage. If damage is visible, immediately contact the shipper and request assistance. Otherwise, proceed with unpacking. Keep the original packing material in case you need to return the product for repair or transport it to another location.
  • Page 6 6 Industrial Integrated Display Computers with Keypad Mounting Clearances Allow adequate space around the computer for mounting, air flow, connections, and maintenance. Sufficient airflow throughout the system unit is required to maintain proper cooling. Clearance should be enough to allow convenient installation or removal of peripheral components, such as the optical disc drive.
  • Page 7 Industrial Integrated Display Computers with Keypad 7 Panel Cutout Dimensions The 6180P products must be appropriately mounted in the panel cutout specified below. Model Cut-out Dimensions (HxW), approx. 1200P 279.0 x 450.0 mm (10.98 x 17.72 in.) 1500P 326.4 x 429.3 mm (12.85 x 16.90 in.) Mount the Display Computer in a Panel Mounting clips secure the computer to the panel.
  • Page 8 8 Industrial Integrated Display Computers with Keypad 7. Hand-tighten the mounting clips around the bezel by following the tightening sequence shown below. 8. Repeat this process at least three times until the clips are hand-tight and the gasket is compressed uniformly against the panel. 9.
  • Page 9 Industrial Integrated Display Computers with Keypad 9 Product Dimensions Product dimensions for each display computer model are given in mm (in.) 1200P Integrated Display with Keypad 445 [17.5] 427 [16.8] 225 [8.9] 483 [19.0] 215 [8.5] 1500P Integrated Display with Keypad 427.20 [16.83] 225 [8.9] 483 [19.0]...
  • Page 10: Connect Peripherals

    10 Industrial Integrated Display Computers with Keypad Connect Peripherals The illustration shows the I/O port panel of the computers. Peripheral components compatible to each port are marked inside the callout figures. The 1200P and 1500P computers have USB ports on both the I/O port side panel and the front access door.
  • Page 11: Connect Ac Power

    Industrial Integrated Display Computers with Keypad 11 Connect AC Power A grounded 3-prong inlet IEC320-C14 power cord provides power to the computer. The power supply input accepts 90…264V AC and is autoswitching. Operate the computer in an industrial or control room environment, which uses some form of power isolation from the public low-voltage mains.
  • Page 12: Functional Ground Screw

    12 Industrial Integrated Display Computers with Keypad To connect DC power, follow these steps. 1. Secure the DC power wires to the terminal block screws. 2. Secure the ground wire to the GND terminal block screw. 3. Apply 24V DC power to the computer. Functional Ground Screw The use of the functional ground screw is not Side View...
  • Page 13: Connect To The Network

    Industrial Integrated Display Computers with Keypad 13 Connect to the Network The computers have dual Gigabit LAN ports. The computers connect to an Ethernet network, using CAT5 or CAT5E twisted-pair Ethernet cabling with RJ-45 connectors. To prevent performance degradation of Ethernet communication, do not subject the computer IMPORTANT or cables to extreme radiated or conducted high-frequency noise.
  • Page 14 For safety information on handling lithium batteries, see Guidelines for Handling Lithium Batteries, publication AG-5.4. WARNING: To prevent voiding your product warranty, use only Allen-Bradley approved replacement parts and accessories. When installing hardware or performing maintenance procedures that require access to IMPORTANT internal components, we recommend that you first back up all computer data to avoid loss.
  • Page 15 Industrial Integrated Display Computers with Keypad 15 b. Remove the old battery from its socket. 6. Insert the new battery with the positive polarity (+ side) facing up, and make sure that it is seated completely. 7. Observe the post-configuration procedure. a.
  • Page 16: Backlight Assembly Disposal

    16 Industrial Integrated Display Computers with Keypad Backlight Assembly Disposal ATTENTION: The backlight assembly in this unit contains mercury. At the end of its life, this equipment should be collected separately from any unsorted municipal waste. Transport the Product If you need to ship your computer via common carrier or otherwise transport it to another location, you must first uninstall the unit from the panel and place it in its original packing material.
  • Page 17: Specifications

    Industrial Integrated Display Computers with Keypad 17 Specifications Hardware and Electrical Specifications Attributes 6180P-12 and 6180P-15 Models Display Display type Color Active Matrix TFT Touch screen, optional Resistive antiglare Display size, diagonal 1200P 308 mm (12.1 in.) 1500P 381 mm (15.0 in.) Display area (WxH), approx 1200P 246 x 185 mm (9.7 x 7.3 in.)
  • Page 18 18 Industrial Integrated Display Computers with Keypad Environmental Specifications Attribute 6180P-12 and 6180P-15 Models Temperature, operating 0…55 °C (32…131 °F) Temperature, storage -20…60 °C (-4…140 °F) Relative humidity, operating 20…85% without condensation Relative humidity, nonoperating 5…90% without condensation Vibration, operating 0.006 in.
  • Page 19: Additional Resources

    Provides declarations of conformity, certificates, and other certification http://www.rockwellautomation.com/rockwellauto details. mation/certification/overview.page You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Rockwell Automation Publication 6180P-IN001C-EN-P - July 2013...
  • Page 20 Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Table of Contents