To use this chart, first find the capacity (tons) on the left side of chart. To find the pipe size, proceed right to the smallest pipe
size. You can then determine the pressure drop (vertical at line) and velocity (diagonal lines) for the pipe size you selected.
For example, for (2) 7.5 ton units, select 5/8 in. O.D. line.
HCFC 22 Liquid Line Pressure Drop/Velocity
HCFC 22 Liquid Line Pressure Drop (lbs./100 Feet)
10 9 8 7
6
5
4
3
EXAMPLE:
10−TON UNIT
5/8 IN. O.D. LINE 4.25
PSIG DROP PER 100
FEET
275 FPM VELOCITY
10 9 8 7
6
5
4
3
HCFC 22 Liquid Line Pressure Drop (lbs./100 Feet)
Figure 10
Page 11
2
1.5
1.0 .9 .8 .7 .6
2
1.5
1.0 .9 .8 .7 .6
NOTE − Shaded area represents unacceptable velocity range.