Page 1
A I R C O N D I T I O N E R S XC21 DAVE LENNOX SIGNATURE COLLECTION ® R-410A - Two-Stage Compressor - SilentComfort™ Technology E N G I N E E R I N G D A T A Bulletin No.
Fan service access accomplished by removal of fan All models are listed in the GreenSpec Directory, a ® guard. leading resource of environmentally responsible products. For expanded ratings, see www.lennoxdavenet.com. XC21 - 2 to 5 Ton Air Conditioner / Page 2...
Page 3
Low gas pulses during compression reduces operational sound levels. Compressor motor is internally protected from excessive current and temperature. XC21 - 2 to 5 Ton Air Conditioner / Page 3...
Page 4
A Freezestat should be installed on compressors equipped with a low ambient kit. A Compressor Low Ambient Cut-Off should be added to terminate compressor operation below recommended operation conditions. XC21 - 2 to 5 Ton Air Conditioner / Page 4...
Page 5
When installed in the supply air plenum, the discharge air temperature sensor allows the icomfort Touch™ Communicating Thermostat to control low and high stage heating temperatures. Sensor is auto-detected when connected to thermostat. XC21 - 2 to 5 Ton Air Conditioner / Page 5...
Page 6
Suction and liquid line service valves and gauge ports are located inside the cabinet. Refrigerant line connections and field wiring inlets are located in one central area of the cabinet. See dimension drawing. XC21 - 2 to 5 Ton Air Conditioner / Page 6...
Page 7
U.S. Emergency Economic Stabilization Act of 2008, Solar modules are UL listed, CSA certified and meet covering 30% of the cost of the solar modules, including National Electrical Code requirements. installation. XC21 - 2 to 5 Ton Air Conditioner / Page 7...
HACR type breaker or fuse. Remote Outdoor Sensor may be used with an icomfort™-enabled outdoor unit for a secondary (alternate) sensor reading. Sensor may also be used with a conventional XC21 - 2 to 5 Ton Air Conditioner / Page 10...
D - Six Wire Low Voltage (not furnished) 18 ga. minimum All wiring must conform to NEC or CEC and local electrical codes. LENNOX LENNOX HEATING UNIT CONDITIONER AIR HANDLER UNIT XC21 - 2 to 5 Ton Air Conditioner / Page 11...
(781) (117) TOP VIEW BASE SECTION TOP VIEW 39−1/2 (1003) 35−1/2 (902) DISCHARGE ELECTRICAL INLETS 4−1/2 (114) SUCTION LINE INLET LIQUID LINE INLET 18−1/2 (470) 8 (203) 1 (25) XC21 - 2 to 5 Ton Air Conditioner / Page 12...
Page 13
C33-44 37L51 XC21-060 91M02 XC21-024 CBX32M-042 37L51 CX34 upflow coils and all Lennox air handlers (except CB26UH “R”) are shipped with a factory installed TXV. In most cases, no change out of the valve XC21-024 CX34-42 37L51 is needed. XC21-036...
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 15
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 16
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 17
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 18
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 19
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 20
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 21
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 22
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 23
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 24
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 25
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 26
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 27
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 28
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 29
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 30
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 31
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 32
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 33
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 34
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 35
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.
Page 36
25 ft. of connecting refrigerant lines. All ratings include the use of a blower time delay relay (TDR). All Lennox variable-speed furnaces and Air Handlers have time delay capabilities. Other Furnaces and Air Handlers may require an optional time delay relay (58M81) for field installation. See furnace or air handler specifications to determine if relay is needed.