10

3. Specification

3.1. General Specification

General Specification
UL System Power
System Power
Power Dissipation
Current for I/O Module
Isolation
Field Power
Max. Current Field Power Contact
Wiring
Weight
Module Size
Environment Condition
Operating Temperature
UL Temperature
Storage Temperature
Relative Humidity
Mounting
Shock Operating
Vibration/shock resistance
EMC resistance burst/ESD
Installation Pos. / Protect. Class
Product Certifications
Supply Voltage : 24Vdc nominal, Class 2
Supply Voltage : 24Vdc nominal
Supply Voltage range : 15~30Vdc
Protection : Output current limit (Min. 1.5A) Reverse polarity protection
110mA typical @ 24Vdc
1.5A @5Vdc
System Power to internal logic : Non-Isolation
System Power I/O driver : Isolation
Supply Voltage : 24Vdc typical (Max. 30Vdc)
*Field Power Range is different depending on IO Module series.
Refer to IO Module`s Specification.
DC 10A Max.
I/O Cable Max. 2.0mm2(AWG 14)
<167g
54mm x 99mm x 70mm
-20℃ ~ 60℃
-20℃ ~ 60℃
-40℃ ~ 85℃
5% ~ 90% non-condensing
DIN rail
IEC 60068-2-6
Based on IEC 60068-2-6
Sine Vibration
- 10 ~ 25 Hz : 0.5mm
- 50 ~ 150 Hz : 5g
- 150 ~ 1000 Hz : 2g
- Sweep Rate : 1 Oct/min, 50 cycles
Sine Vibration
- 10 ~ 25 Hz : 0.03 g²/Hz
- 25 ~ 50 Hz : 0.05 g²/Hz
- 50 ~ 150 Hz : 0.15 g²/Hz
- 150 ~ 1000 Hz : 0.01 g²/Hz
IEC 60068-2-27
EN 61000-6-2 : 2005
EN 61000-6-4/ALL : 2011
Variable / IP20
UL, CE, RoHS2