The electronic circuits reduced by M.S. are completely safe from electrostatic discharge (8 KV IEC 255.22.2) when housed in their case; withdrawing the modules without proper cautions expose them to the risk of damage. Copyright 2010 - Microener Firmware: 1.0X...
24V(-20%) / 110V(+15%) a.c. 80V(-20%) / 220V(+15%) a.c. a) - b) - 24V(-20%) / 125V(+20%) d.c. 90V(-20%) / 250V(+20%) d.c. Before energising the unit check that supply voltage is within the allowed limits. Copyright 2010 - Microener Firmware: 1.0X...
From ON to OFF, automatically when the lit-on cause disappears. In case of auxiliary power supply failure the status of the leds is recorded and reproduced when power supply is restored. Copyright 2010 - Microener Firmware: 1.0X...
Each relay is identified by its programmable address code (NodeAd) and can be called from the P.C. A dedicated communication software (MSCOM) for Windows 95/98 (or later) is available. Please refer to the MSCOM instruction manual for more information. Microelettrica Scientifica. Copyright 2010 - Microener Firmware: 1.0X...
Complete test activated by the keyboard or via the communication bus either with or without tripping of the output relays. If any internal fault is detected, the display shows a fault message, the Led "PROG/IRF" illuminates and the relay R5 is deenergized. Copyright 2010 - Microener Firmware: 1.0X...
- Yellow key ENTER/RESET : It allows the validation of the programmed settings - the actuation of test programs - the forcing of the default display indication - the reset of signal Leds. e) - Indirect key : Enables access to the programming. Copyright 2010 - Microener Firmware: 1.0X...
Highest current of phase A during the first 100ms, displayed as p.u. of C.Ts rated current xx.x As above, phase B xx.x As above, phase C x.xx As above, unbalance compensated voltage Copyright 2010 - Microener Firmware: 1.0X...
Enter the mode "SET DISP", select the menu "SETTINGS" or "F RELAY", scroll information available in the menu by keys "+" or "-". SETTINGS= values of relay's operation parameters as programmed RELAY= output relays associated to the different functions as programmed. Copyright 2010 - Microener Firmware: 1.0X...
Trip level of high-set overcurrent element 0.2 - 2 - Dis 0.01 (p.u. of the rated current of the phase C.Ts.) Trip time delay of the high-set overcurrent element (0.1-99.9) 0.1 – 6500 (100-6500) Copyright 2010 - Microener Firmware: 1.0X...
Page 13
Max reset time delay of the instantaneous element after 0.1-0.75 tripping of the delayed element Identification number for the connection on serial NodAd 1 - 250 communication bus The setting Dis indicates that the function is disactivated. Copyright 2010 - Microener Firmware: 1.0X...
(tBIf Dis) or (tBf 2xtBf); even with the blocking input still present, it only lasts for the set trip time delay of the function plus an additional time 2xtBf 2tBF As above for the unbalance functions Copyright 2010 - Microener Firmware: 1.0X...
Switch off the capacitors. Set for Ic and αc the values Iu αu When the capacitors are switched on again, the values Iu, αu displayed remain practically unchanged, while the value of Id will be nearly zero. Copyright 2010 - Microener Firmware: 1.0X...
This is extremely important as discharges eventually tacking place in parts or components of the board can severely damage the relays or cause damages, not immediately evident to the electronic components. Copyright 2010 - Microener Firmware: 1.0X...
Microelettrica Scientifica S.p.A. - 20089 Rozzano (MI) - Italy - Via Alberelle, 56/68 Tel. (##39) 02 575731 - Fax (##39) 02 57510940 http://www.microelettrica.com ute@microelettrica.com e-mail : The performances and the characteristics reported in this manual are not binding and can modified at any moment without notice Copyright 2010 - Microener Firmware: 1.0X...
18. WIRING THE SERIAL COMMUNICATION BUS (SCE1309 Rev.0) 19. CHANGE PHASE CURRENT RATED INPUT 1 OR 5A Connector Jumper Rated Input Phase A Current Rated Input Current Phase B Input Rated Current Phase C Copyright 2010 - Microener Firmware: 1.0X...
Slide-in the card on the rails provided inside the enclosure. Plug-in the card completely and by pressing the handle to the closed position. Rotate anticlockwise the screws and with the mark in the vertical position (locked). Copyright 2010 - Microener Firmware: 1.0X...
The input for blocking the operation of the time delayed elements relevant to unbalance (UH, UL) Breaker failure alarm 2tBF 2tBF As above for the unbalance functions Commissioning Engineer : Date : Customer Witness : Date : Copyright 2010 - Microener Firmware: 1.0X...