6.1

Heat

To set various water &
ambient temperatures for
heating.
Default Setting
Setting Options / Display
Water temp. for heating ON /
Outdoor temp. for heating OFF /
T for heating ON /
Outdoor temp. for heater ON
Water temp. for heating ON
Heating ON
Compensation
temperatures in
curve
compensation curve or
direct input.
Water temp. for heating ON Compensation curve
Input the 4 temperature
X axis: -5 °C, 15 °C
points
Y axis: 55 °C, 35 °C
(2 on horizontal X axis,
2 on vertical Y axis).
• Temperature range: X axis: -15 °C ~ 15 °C, Y axis: See below
• Temperature range for the Y axis input depends on the model:
1. WH-SDC model : 20°C ~ 55°C
2. WH-SHF model & Back up heater is enabled: 25°C ~ 65°C
3. WH-SHF model & Back up heater is disabled: 35°C ~ 65°C
4. WH-SXC model : 20°C ~ 60°C
• If 2 zone system is selected, the 4 temperature points must also be input for Zone 2.
• "Zone 1" and "Zone 2" will not appear on the display if only 1 zone system.
Water temp. for heating ON Direct
Temperature for heating
35 °C
ON
• Min. ~ Max. range is conditional as follows:
1. WH-SDC model : 20°C ~ 55°C
2. WH-SHF model & Back up heater is enabled: 25°C ~ 65°C
3. WH-SHF model & Back up heater is disabled: 35°C ~ 65°C
4. WH-SXC model : 20°C ~ 60°C
Outdoor temp. for heating OFF
Temperature for heating
24 °C
OFF
19