VOLTAGE
UNIT
V-PH-HZ
SIZE 50JZ
MIN MAX
024
208/230–1–60 187
030
208/230–1–60 187
036
208/230–1–60 187
042
208/230–1–60 187
048
208/230–1–60 187
060
208/230–1–60 187
* Heater capacity (kW) based on heater voltage of 208-v & 240-v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
Refer to Multiplication Factors Table 23.
Table 10—50JZ with ICM FIOP Electrical Data
OUTDOOR
COMPRESSOR
RANGE
RLA
LRA
253
13.5
61.0
253
15.9
73.0
253
16.9
83.0
253
22.4
105.0
253
21.3
109.0
253
27.6
158.0
INDOOR
ELECTRIC
FAN
FAN
MOTOR
MOTOR
FLA
FLA
Nominal kW*
-/-
3.8/5.0
0.9
4.3
5.4/7.2
7.5/10.0
-/-
3.8/5.0
0.9
4.3
5.4/7.2
7.5/10.0
11.3/15.0
-/-
3.8/5.0
1.6
6.8
5.4/7.2
7.5/10.0
11.3/15.0
-/-
3.8/5.0
5.4/7.2
0.9
6.8
7.5/10.0
11.3/15.0
15.0/20.0
-/-
3.8/5.0
5.4/7.2
1.6
6.8
7.5/10.0
11.3/15.0
15.0/20.0
-/-
3.8/5.0
5.4/7.2
1.6
9.2
7.5/10.0
11.3/15.0
15.0/20.0
22
SINGLE POINT
HEAT
POWER SUPPLY
FLA
MCA
-/-
22.1/22.1
18.1/20.8
44.6/48.1
25.9/30.0
54.5/59.6
36.1/41.7
67.2/74.2
-/-
25.1/25.1
18.1/20.8
47.6/51.1
25.9/30.0
57.4/62.6
36.1/41.7
70.2/77.2
54.2/62.5
92.8/103.2
-/-
29.5/29.5
18.1/20.8
52.1/55.6
25.9/30.0
61.9/67.0
36.1/41.7
74.7/81.6
54.2/62.5
97.2/107.7
-/-
35.7/35.7
18.1/20.8
58.3/61.7
25.9/30.0
68.1/73.2
36.1/41.7
80.8/87.8
54.2/62.5
103.4/113.0
72.2/83.3
126.0/139.9
-/-
35.0/35.0
18.1/20.8
57.6/61.1
25.9/30.0
67.4/72.5
36.1/41.7
80.2/87.1
54.2/62.5
102.7/113.2
72.2/83.3
125.3/139.2
-/-
45.1/45.1
18.1/20.8
67.7/71.1
25.9/30.0
77.7/82.8
36.1/41.7
90.2/97.2
54.2/62.5
112.8/123.2
72.2/83.3
135.4/149.3
MAX FUSE
MOCP
OR CKT. BKR.
30/30
–
50/50
–
60/–
–/70
–
70/80
30/30
–
60/60
–
–
70/70
–
80/80
–
100/110
40/40
–
60/60
–
–
70/80
–
80/90
–
100/110
50/50
–
–
70/70
–
80/80
–
90/90
–
110/125
–
150/150
50/50
–
–
70/70
–
80/80
–
90/90
–
110/125
–
150/150
60/60
–
–
80/80
–
90/90
–
100/110
–
125/125
–
150/150