Safety instruction 1.3. How to use this Manual Attention that needs to be paid when operating and maintaining ATESS ATS model. Read this manual before installation of the ATESS ATS. Store this manual whereaccessible at all times. Product description The contents of this manual will be periodically updated or revised if necessary.
Proper installation requires following all the instructions in the user manual involving DANGER indicates a hazard with a high level of risk which, if not transportation, mounting, wiring and commissioning. ATESS does not cover avoided, will result in death or serious injury.
3.1 ATS ATS produced by ATESS is designed to work with ATESS HPS hybrid inverter. It mainly enables HPS system to connect with diesel generator and power grid at the same time. Grid...
If necessary, you can seek help from ATESS Customer Service department. Caution ATESS ATS50 can only be stored when it is stopped and all the doors are closed in a 3.4.2. Packing information dry room to protect the internal circuits against dust and moisture.
Installation In front of the installation place of ATS, a space of 1.1m or more shall be ensured, the back 1.1m or more, the top 0.5m or more to ensure easy installation, cooling and maintenance. 5.1 Installation condition requirements Cable trench The cable connection of ATS adopts bottom inlet and bottom outlet.
Demolish the front and back cover lids of the pedestal; Note 1: ATS is integrated and cannot be dissembled either in transportation or installation. Any fault attributed to modification unauthorized by the ATESS is beyond the quality assurance. ② Screw off the hold-down nuts at the bottom of the wood pallet;...
Cable requirements 1. Please select the corresponding withstand voltage cable according to the voltage level. 2. The current will change due to different voltage value. Please calculate the corresponding cable diameter according to the actual voltage range. The following table only provides cable requirements for the minimum operating voltage for your reference.
Page 10
5.4.2 AC side wiring 5.4.4 Earthing ATS must be earthing well for safety; Please make sure of the connection between PE in power Caution, risk of danger distribution cabinet and PE copper in ATS good; and make sure the earthing cable more than half of load When connecting the AC grid, cut off the circuit breaker at the AC side to ensure that the cable, and earthing resistance is not lower than 4Ω.
Maintenance and modification Other inspection Only personnel authorized by ATESS can maintain and modify ATS. To ensure personal safety, please use All useless conductive parts shall be tied with insulating ties. only the original components provided by the manufacturer. Otherwise there will be no guarantee on There are no tools, parts, conductive dust or other foreign matters left inside the cabinet.
CAUTION! 1. After power off, wait for 5 minutes to confirm the safety before maintenance. 2. When safety assured, the disassembly and assembly work could be 8.1 Specification carried out . Parameter ATS30 ATS50 ATS100 ATS150 Nominal voltage 400V 400V...
Warranty conditions In the event of failure during the warranty period, ATESS will repair or replace the product free of charge; The failed machine shall be owned by ATESS; the customer shall Set aside some time to repair the faulty machine.