Configuring converters / MasterCAN RS2CAN configuration for data conversion from Modbus RTU registers into SPN 3.8 MasterCAN RS2CAN configuration for data conversion from Modbus RTU registers into SPN The submenu of MODBUS-CAN Gate FM of Service S6 MasterCAN software serves to configure...
Page 36
Configuring converters / MasterCAN RS2CAN configuration for data conversion from Modbus RTU registers into SPN • The dropdown list Function Code (SPN 521682) serves to select the required function of reading Modbus RTU registers (if the value is not specified, the Error is displayed) (see the admissible values of the function code in table 6).
Page 37
Configuring converters / MasterCAN RS2CAN configuration for data conversion from Modbus RTU registers into SPN Examples: a) In case the value of the Parameter from the register is read in bars and the output SPN is specified in kPa, then, taking into account the correlation 1 bar=100 kPa, the factor base value should be multiplied by 100.
Page 38
Configuring converters / MasterCAN RS2CAN configuration for data conversion from Modbus RTU registers into SPN • The field S6 Address (SA) (SPN 521188) serves to specify the unique network address CAN j1939/S6 Telematics interface Unit which generates the selected or for which the request for reading the selected SPN is needed.