Hose And Accessories Installation; General; Balance Vapor Recovery - Wayne Reliance G6101D Installation & Operation Manual

S1 ast mechanical registration fleet dispensers
Table of Contents

Advertisement

3.4

Hose and Accessories Installation

3.4.1

General

Hose assemblies should be U.L. Listed and installed in accordance with the manufacturer's
instructions.
Install the hose assembly after the dispenser is installed.
To ensure a proper joint, wash all cutting oil off the threads and use a U.L. Listed
o
gasoline-resistant pipe joint sealing compound.
Place the compound on male threads only; be careful not to get any excess compound
o
on the inside of the fittings.
Install the fixed end of the hose to the dispenser outlet; secure according to the
o
instructions of the sealing compound and hose manufacturer.
Install the nozzle, and other hose accessories – swivels, breakaways, etc. – on the hose
o
according to the manufacturer's instructions.
NOTE: Do not use the joint sealant compound on balanced vapor recovery
accessories. Reference the manufacturer's instructions.
NFPA code requires a Listed emergency breakaway device, designed to retain liquid on
both sides of the breakaway point, to be installed on each hose. These devices must be
installed and maintained per the manufacturer's instructions. Refer to your state and local
codes for breakaway device requirements that apply to your installation.
NOTE: Models with "E" prefix, for dispensing up to and including E85, must use only the
following hose and accessories. All connections for these devices must use UL
Classified Saf-T-Lok Teflon pipe sealant:
OPW hose nozzle valves models: 21GE, 21GEA
OPW breakaway model: OPW 66V-0492
OPW swivel connector model: 241TPS-0492
Veyance Technologies hose assembly model: Flexsteel Futura Ethan-All
WARNING
Use only UL Listed hoses, nozzles, breakaways, and other hose accessories. Continuity must
be present between the dispenser outlet and nozzle spout to prevent static discharge while
fueling. Continuity must be checked for the outlet/hose assembly to insure that the nozzle is
grounded. Failure to do so may result in a hazardous condition that could cause serious injury
or death.
3.4.2

Balance Vapor Recovery

The nozzle hook/boot assembly can accommodate an Emco Wheaton A4015 Short Spout or
a Husky V Short Spout nozzle without modification.
The vapor recovery installation should follow the instructions supplied by the manufacturer
for the vapor recovery components and should comply with all codes, both local and
national.
The discharge elbow can be oriented upwards for piping to an overhead splitter.
920943
Rev E
July 2014
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents