Page 1
4042660 - Mini Ceiling HEPA Ceiling HEPA Filter Box Mini Standard The Santa Fe Ceiling HEPA is an air purifier that Serial Number utilizes a HEPA grade filter. The unit is installed in a Install Date drop/open ceiling to provide clean air to a space.
Filter Media .................... 6 Assembly ....................6 Hanging the Santa Fe Ceiling HEPA Fan Box ........6 Ducting To and From the Santa Fe Ceiling HEPA ......... 6 Wiring the Santa Fe Ceiling HEPA ............7 Operation ....................8 Adjusting the Amount of Air Flow ............8 Maintenance ....................
Page 3
CAUTION! THIS SYMBOL MEANS IMPORTANT INSTRUCTIONS. FAILURE TO HEED THEM CAN RESULT IN INJURY OR MATERIAL PROPERTY DAMAGE. Registrations The Santa Fe Ceiling HEPA conforms to unified standard UL 507:2017 Ed.10+R:15 and CSA C22.2#113:2015 Ed.10+U1. WARNING! WARNING! 120 VOLTS MAY CAUSE SERIOUS INJURY FROM ELECTRIC SHOCK.
20.7” x 20.6” x 6.8” (without the duct collar) and x 8.7” (with the duct collar attached) Unit Weight 45 lbs. (Standard Ceiling HEPA) 25 lbs. (Mini Ceiling HEPA) Santa Fe Ceiling HEPA Installation & Operation Instructions Santa-Fe-Products.com | 800.533.7533...
Location of the Santa Fe Ceiling HEPA • The Santa Fe Ceiling HEPA fan boxes must be installed 4’ to 12’ from the Santa Fe Ceiling HEPA filter box. The boxes are to be connected with 10” insulated flexible ducting. The fan box should be connected with as straight duct path as possible.
Inlet Outlet Filter Media • 20”x20”x1” MERV-8 or equivalent pre-filter must be used and maintained in the Santa Fe Ceiling HEPA filter box to prevent depris from entering the Santa Fe Ceiling HEPA fan box. Assembly • Assemble the supplied 10” duct collars with self threading screws. Duct collars on the fan outlets (square hole) must be positioned such that they do not obstruct air flow.
National Electrical Code. The Santa Fe Ceiling HEPA uses a 115 volt, 10 amp circuit which is connected to the black and white wires in the electrical cabinet (see Fig. 3). Additionally, the included grounded power cord may be used in non-plenum rated space above the drop ceiling provided 115 Volt grounded outlet is available.
VENTILATION. DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS AND VAPORS. OPERATION The Ceiling HEPA fan boxes are to be used with the Santa Fe Ceiling HEPA system only. No other use is allowed. Adjusting the Amount of Air Flow •...
Blower Operates on One Speed Only • If the blower motor fails to operate when voltage is present at its leads, the motor is defective and the blower must be replaced. 800.533.7533 | Santa-Fe-Products.com Santa Fe Ceiling HEPA Installation & Operation Instructions...