Siemens SDV6 Instruction Manual page 35

Distribution circuit breaker 15.5 kv, 27.6 kv and 38 kv
Table of Contents

Advertisement

Problem
Circuit breaker fails to close.
Maintenance and troubleshooting
Symptoms
Closing spring will not automatically charge.
Closing springs
Closing coil or solenoid
charge, but circuit
(52SRC) fails to
breaker does not close.
energize. No sound of
circuit breaker closing.
Closing coil energizes.
Sound of circuit breaker
closing is heard but
circuit breaker contacts
do not close.
Table 8: Troubleshooting
Possible causes and remedies
1. Secondary control circuit is de-energized or
control circuit fuses are blown. Check and
energize or replace if necessary.
2. Damage to wiring, terminals or connectors.
Check and repair as necessary.
3. Failure of charging motor (88). Replace if
required.
4. Motor cut-off switch LS21 or LS22 fails to
operate. Replace if necessary.
5. Mechanical failure of operating mechanism.
Check and contact regional service centers,
the factory or telephone Siemens field
service at +1 (800) 347-6659 or +1 (919)
365-2200 outside the U.S.
1. Secondary control circuit de-energized or
control circuit fuses blown. Correct as
indicated.
2. No closing signal to XOA2. Check for
continuity and correct protective relay logic.
3. Failure of anti-pump relay (52Y) contacts 21
to 22, 31 to 32 or 13 to 14. Check and
replace as required.
4. Failure of close coil (solenoid) (52SRC).
Check and replace as required.
5. Auxiliary switch NC contacts 41 to 42 are
open when circuit breaker contacts are
open. Check linkage and switch. Replace or
adjust as necessary.
6. Spring-charged switch LS9 NO contacts
remain open after springs are charged.
Check and replace as required.
1. Mechanical failure of operating mechanism.
Check and contact regional service centers,
the factory or telephone Siemens field
service at +1 (800) 347-6659 or +1 (919)
365-2200 outside the U.S.
35