LOW GAS PRESSURE REGULATOR WITH OR
WITHOUT INCORPORATED SAFETY SHUT-OFF DEVICE
TYPE: 121
(shut-off device:
- for high pressure – VP
- for high and low pressure –VNP)
REGULATOR NISKOG PRITISKA BEZ I SA
BLOKADNIM MEHANIZMOM TIP: 121
(blokada od: - visokog pritiska – VP
- visokog i niskog pritiska - VNP)
SAFE USE GUIDE
UPUTSTVO ZA MONTA@U, RUKOVANJE I ODR@AVANJE

Advertisement

Table of Contents
loading

Summary of Contents for GasTeh 121

  • Page 1 - for high pressure – VP - for high and low pressure –VNP) REGULATOR NISKOG PRITISKA BEZ I SA BLOKADNIM MEHANIZMOM TIP: 121 (blokada od: - visokog pritiska – VP - visokog i niskog pritiska - VNP) SAFE USE GUIDE...
  • Page 2: General Remark

    Tehnički katalog (GT-121-01). GENERAL REMARK Regulators type: 121 and type 121-BV are devices whose function is to maintain the value of the controlled pressure within its tolerance field irrespective of disturbance pressure. Regulators type: 121 and type 121-BV are direct acting regulators in which the net force required to move the control member is supplied by the controlled pressure.
  • Page 3 Fail- to- open stand- alone regulators cannot be used as a safety accessory according to PED 2014/68/EC to protect downstream pressure equipment. According to PED 2014/68/EC gas pressure regulators type 121 and 121- BV depending of their size are in the following groups:...
  • Page 4 1,1 x PS. Regulators type 121 and type 121- BV are not used as stand- by monitor and are not equiped with any external visual device which indicates wheather the control member is in the closed or in fully open position.
  • Page 5 MARKING OF REGULATOR TYPE: 121 AND TYPE: 121-BV / OZNAČAVANJE REGULATORA TIP: 121 I TIP: 121-BV The nameplate shall contain all basic informations about mentioned products. / Tablica regulatora mora sadržati sve potrebne informacije o osnovnim karakteristikama regulatora. Table 2. / Tabela 2.
  • Page 6 Opseg pritisaka blokiranja: - za visoke pritiske: 0.03 ÷ 1 bar (klasa tačnosti AG 2.5) - za niske pritiske: 0.002 ÷ 0.3 bar (klasa tačnosti AG 5) Vreme odziva: ≤1s Temperature class: 2 (-20°C ÷+60°C) GT-121-02...
  • Page 7: Overpressure Protection

    ZAŠTITA OD PREVISOKOG PRITISKA Preporučeni maksimalni dozvoljeni pritisci su naznačeni na tablici regulatora. Ako regulator nema ugrađen blokadni mehanizam, mora se predvideti neka druga vrsta zaštite od previsokog pritiska. Posle svakog prekoračenja pritiska, potrebno je izvršiti pregled regulatora zbog mogućih oštećenja. GT-121-02...
  • Page 8: Installation

    - make shure that data on regulator plate is compatible with operating requirements - make shure that arrow on regulators body and flow are in the same directions Pressure regulators shall be instaled in non- seismic area and hasn´t to undergo fire and must be provided cathodic protection and electrical isolation. GT-121-02...
  • Page 9 Picture 1. / Slika 1. Installation / Ugradnja Regulator can be mounted in other position if required (consult GasTeh personel for advice). Before start-up regulator, impulse connections must be connected with the main pipeline. This connections shoud be made using stainless steel or cooper pipe with minimum internal diameter of 8 mm.
  • Page 10: Puštanje U Rad

    Za podešavanje izlaznog pritiska potrebno je prvo skiniti poklopac (18) sa kućišta opruge (23). Okretanjem pritezača opruge (17) u smeru kazaljke na satu dolazi do povećanja izlaznog pritiska, dok okretanjem u suprotnom smeru, izlazni pritisak opada. Podešavanje pritiska se prati na manometru iza regulatora. GT-121-02...
  • Page 11: Checks And Maintenance

    If outlet pressure increase, more than defined in lock-up pressure class (AG), slowly close inlet valve and call service personel from GasTeh to carry out general maintenance of regulator. For checking function of regulator, slowly close outlet valve, and open relief valve downstream the regulator, and check pressure oscilating.
  • Page 12 - install pressure gauge downstream of regulator - set outlet pressure by rotating adjusting ring (17) - if necessary replace spring (38) - set safety shut-off device pressure PREGLEDI I ODRŽAVENJE UPOZORENJE! Održavanje mogu da izvode samo stručna i osposobljena lica. GT-121-02...
  • Page 13 Regulator je potrebno servisirati i u tom slučaju pozovite stručno osoblje iz GasTeh-a. Za proveru rada regulatora, zatvorite izlaznu slavinu iza regulatora i pomoću odušne slavine posle regulatora, otvaranjem iste, proveriti rad regulatora.
  • Page 14 - proveriti nedozvoljeno isticanje gasa pomoću sapunice Podešavanje posle montaže Posle montaže, potrebno je podesiti vrednost izlaznog pritiska na sledeći način: - postaviti manometar na liniju iza regulatora - podesiti izlazni pritisak okretanjem pritezača opruge (17) - ukoliko je potrebno zameniti oprugu odgovarajućom GT-121-02...
  • Page 15 (is not possible to (04) (Pic.4.)/ Zubac (03) je Clean or replace / deactivate) / Blokadni zaglavljena u nosaču brave (03) Očistiti ili zameniti mehanizam je aktiviran i ne može (Slika 4.) se deaktivirati Table 4. / Tabela 4. GT-121-02...
  • Page 16 Retaining ring / Uskočnik S270MC Nozzle / Dizna CW614N Body / Kućište regulatora Vent valve diaphragm / Membrana 745 YG 290 ASTM A razrezana 352LCB Part name / Naziv pozicije Material Part name / Naziv pozicije Material Table 5. / Tabela 5. GT-121-02...
  • Page 17 21. Screw / Zavrtanj Class 8.8 EN AW 2030 01. Lower blockade housing / Kuć. blokade donje 20. Cover / Poklopac AlSi10Mg Part name / Naziv pozicije Material Part name / Naziv pozicije Material Pos. Pos. Table 6. / Tabela 6 GT-121-02...
  • Page 18 Lock carrier cover / Poklopac nosač brave CW614N Lever / Poluga CW614N Lock carrier / Nosač brave CW614N Tooth / Zubac X20Cr13 Spring housing / Kućište opruge CW614N Rod / Trn X5CrNi18-10 Pos. Part name / Naziv pozicije Material Table 7. / Tabela 7. GT-121-02...
  • Page 19 For inlet pressure of 0,5 to 1 bar a reduction ring is installed / Za ulazne pritiske od 0,5 do 1 bar ugrađuje se redukcioni prsten. For all regulators of type 121 and 121-BV, the reduction ring is the same / Za sve regulatore tipa 121i 121-BV redukcioni prsten je isti.
  • Page 20: Spare Parts

    Skladištenje rezervnih delova treba da je u skladu sa domaćim standardima, kako bi se izbegla oštećenja rezervnih delova. Prostor za skladištenje treba da je bez vlažnosti, sa prosečnom temperaturom i sa dovoljno prostora da se izbegnu bilo kakva oštećenja rezervnih delova. "GasTeh" d.o,o. Kralja Petra I b.b. 22320 Indjija...

This manual is also suitable for:

Visokog

Table of Contents