Order No.: 421 404 / 421 405 1. Introduction Thank you for choosing a spega product. This product has been designed and optimized for use in room automation. To familiarize yourself with the handling and functionality of the system, we would ask you to read this manual carefully. It contains information about the operation, assembly and parameterization of the system.
Electrical devices must be assembled and installed by trained personnel only. Operation of the device is determined by the application software. Only software which has been approved by spega should be used for this device. The system integrator should ensure that the software and relevant parameterization correspond with the wiring and intended use of the device.
Order No.: 421 404 / 421 405 2. Product description The modules clima BSK4-F and clima BSK4-F230 are used as actuators to integrate up to 4 fire dampers or smoke dampers with spring return drive into LON networks. The difference between both types of modules is the type of power supply. The module clima BSK4-F is supplied with 24V AC or DC, the module clima BSK4-F230 is mains- operated (230V AC).
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 2.1. Technical Data clima BSK4-F Power supply Operating voltage 24V AC/DC Current input max. 180 mA Network Type of network...
Page 8
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Display elements Service LED Device status Communication LEDs Activity during transmission/reception on the LON bus LED status indicators Status of binary inputs...
Page 9
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 clima BSK4-F230 Power supply Operating voltage 230V AC Current input max. 4,5 VA Network Type of network TP/FT-10 (78kbps) Type of transceiver...
Page 10
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Housing Type of protection IP 65 (DIN 40050 / IEC 144) Dimensions 63 x 254 x 180 mm (H x W x D)
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 2.2. Mounting The device is designed for Safety Extra Low Voltage (SELV). Electrical devices must be assembled and installed by trained personnel only.
Connection of clima BSK4-F The module clima BSK4-F provides a TP/FT-10 transceiver to connect to a free- topology LON network. The module is supplied by 24V AC or DC. The module power supply is identical to the motor supply. Please use the following...
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Connection of clima BSK4-F230 The module clima BSK4-F230 provides a TP/FT-10 transceiver to connect to a free- topology LON network. The module is supplied by 230V AC. The module power supply is identical to the motor supply.
The present product uses a processor of a newer generation for which the application download is only supported from LNS version 4.02. For this reason, with lower LNS versions you also need the Spega Update Tool, which you can download from the download area on our homepage www.spega.de.
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 2.6. Operation The operating elements described below are available for commissioning and maintenance of the fire dampers actuator modules. Service button The service button is used to send the neuron ID of the actuator module.
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Input LEDs The input LEDs E1/1 to E4/2 indicate the status of the connected limit position switches of the dampers.
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 3. Applications This document describes the behaviour and parametrisation of the applications listed below. The applications are split into logical objects according to LonMarkTM- Interoperability-Guidelines.
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 3.3. Description of software objects The individual functional objects are described in greater detail below. 3.3.1 NodeObject Interface description Network interface Version 4.01...
Page 20
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Configuration parameters SCPTdevMajVer Major version of SCPTdevMinVer Minor version of application application Type: SCPT #165 (read only) Type: SCPT #166 (read only)
Page 21
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 the network variable nvoStatus. The following commands are to be used for the status request: nviRequest Meaning {RQ_UPDATE_STATUS, 0} determining the status of the device...
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 3.3.2 FireSmokeDamperActuator The fire damper object of the e.control system can be used both for smoke dampers (ERK) and fire dampers (BSK). The object has a control value input with feedback, a position detection and an integrated runtime check.
Page 23
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Network variables Input variables nviDuctPos Channel ored position nviDriveValue Control input of actuator (comes from the front Type: SNVT_hvac_emerg of the chain)
Page 24
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 nvoUpSwitch state output of first nvoDownSwitch state output of second end-position switch end-position switch (normal position) (safety position) Type: SNVT_switch...
Page 25
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Configuration parameters UCPTfireSD Type of damper - end UCPTswitchMap Assignment of the end- positions and control position switches or the...
Page 26
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 SCPTmaxRcv Maximum time for SCPTmaxSend Maximum period of Time Time receiving values on time between sending nviDriveValue to detect two telegrams, used for...
Page 27
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Intended use The dampers can be used as fire or smoke dampers. The main difference lies in the specified safety position. The setting of the intended use of the connected damper must be made via the configuration parameter SCPTdirection.
Page 28
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Position detection The position detection is based on the end position switches. Allocation of the end position switches The parameter UCPTswitchMap can be used to specify to which binary inputs the end position switches to be used are connected.
Page 29
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Damper condition nvoDrivePos End position switch (normally open contact) “OPEN” „CLOSED“ „OPEN“ „CLOSED“ EMERG_NORMAL closed(1) open(0) „CLOSED“ ”OPEN” EMERG_FIRE open(0)
Page 30
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Receive and transmit times Maximum receiving time For the set input nviDriveValue it can be set in the parameter SCPTmaxRcvTime in which minimum intervals an updated value is expected.
Page 31
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Status of the binary input Value of the network variable open (0,0) closed (1,100) Maintenance function With the help of the integrated maintenance function, the functionality of the damper can be specifically tested.
Page 32
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 status on the nvoDriveStatus. If the protection position is reached by the end of the phase, the second phase starts. When returning to the normal position the compliance with the running time specified in SCPTdriveTime is checked.
Page 33
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 checked cyclically every 100 milliseconds and when the end position switches are changed. The following states can be read in the status:...
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 3.3.3 FireCompartmentGroup The fire compartment group object of the e.control system is used to control fire damper objects of the same device module in groups. In this way, dampers of the same fire compartment can be controlled together.
Page 35
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Network variables nviGroup Control input of fire Value compartment group Type: SNVT_hvac_emerg Range of listed values of emerg_t: values: EMERG_NORMAL...
Page 36
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Group allocation To allocate an FSDActuator object to the group, the bit allocated to the object must be set in the UCPTfcGroupMembers parameter. To simplify the calculation of the decimal value for the UCPTfcGroupMembers, the values of the desired members entered in the table must be added together.
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 4. Glossary alternating current Alias entry address entry for a member of a group binding in the sending node amplitude shift keying...
Page 38
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Short address individual address for identification of DALI devices light emitting diode LonWorks network services LON™ local operating network LonMark™...
Page 39
Manual for clima BSK4-F / clima BSK4-F230 LON fire damper actuator 4 ports Order No.: 421 404 / 421 405 Transmitter ID individual, unique 32-bit transmitter identification for wireless transmitters, based on EnOcean technology UCPT user configuration property type UNVT user network variable type ‚VDE Verband der Elektrotechnik, Elektronik und...
Need help?
Do you have a question about the BSK4-F and is the answer not in the manual?
Questions and answers