1-8. ELECTRONIC EXPANSION VALVE CONTROL

The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the following values.
The compressor frequency, the temperatures detected by the discharge temperature sensor
and the outdoor temperature sensor.
AO*G72/90LRLA
At the time of supplying the power to the outdoor unit, the initialization of the electroni c
expansion valve is operated (528 pulses are input to the closing direction).

1-9. TEST OPERATION CONTROL

With Wired Remote Controller
With "Monitor Mode Screen" displayed, press and hold the [MENU] button,
[<] button and [ENTER] button simultaneously for at least 2 seconds.
Setting item selection screen is displayed.
Select the number"09" of the item to be set with the [< ] or [> ] button,
press the [ENTER] button to switch to the Setting Screen.
The test operation screen is displayed.
Press the [ENTER ] button to test operation begins.
Test operation is completed after about an hour.
The test run will automatically end is approximately 60 min.
With Wireless Remote Controller
U
nder the condition where the air conditioner runs, press the TEST RUN button, and
the test operation control mode will appear.
During test running, the operation lamp and timer lamp of the air conditioner body twinkle simultaneously.
Set the test operation mode, and the compressor will continue to run regardless of whether the room
temperature sensor detects.
The test operation mode is released if 60 minutes have passed after setting up the test operation.

1-10. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )

The compressor won't enter operation status for 3 minutes after the compressor is stopped,
even if any operation is given.

1-11. 4-WAY VALVE EXTENSION SELECT

At the time when the air conditioner is switched from the cooling mode to heating mode,
the compressor is stopped, and the 4-way valve is switched in 3 minutes later
after the compressor stopped.

1-12. AUTO RESTART

When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically resumed with
the memorized operation contents.
When the power is interrupted and recovered during timer operation, timer operation is canceled,
but only setting time is memorized.
[Operation contents memorized when the power is interrupted]
Operation mode
Set temperature
Set air flow
Timer mode and timer time (set by wireless remote controller)
°
10
C HEAT (set by wireless remote controller)
The pulse range of the electronic expansion valve control is
50 ~ 500 pulses (Cooling) and 50 ~ 500 pulses (Heating).