wirinG anD DiMenSiOnS
Typical electrical connections are shown in the Wiring diagram below. Connecting cables carry low current and do not require special sized
wire. The connection between the speed controller and the synchronizer Terminal 6 is sensitive and must be shielded for its entire length.
The shield must be connected at one end only and must be terminated to the case.
Phasing of main power (MAINS) and the generator signals occurs when Terminals 1 and 3 are in phase.
Paralleling out-of-phase generators may cause equipment damage.
High AC Voltage may be present at Terminals 1 thru 4. De-energize and check voltages before use.
3
Governors America Corp. © 2021 Copyright All Rights Reserved
SYC6714 03-2021-B2