inStaLLatiOn
The SYC6714 can be mounted in a cabinet with other equipment. Limit exposure of the unit to extreme temperatures. Mount the
SYC6714 vertically if exposed to moisture or wetness to prevent accumulation inside the unit.
The governor system must be in good working order and adjusted correctly for the synchronizer to properly operate in the system. The
SYC6714 is factory set to near optimum settings, therefore, large increment adjustments are not normally needed.
An overspeed shutdown device, independent of the governor system, should be used to prevent loss of
engine control which may cause personal injury or equipment damage.
Do not rely exclusively on the governor system electric actuator to prevent overspeed. A secondary shut-
off device, such as a fuel solenoid must be used.
Since the SYC6714 is a CE (Community Europe) approved unit, if used as a CE unit, all GAC installation requirements in-
cluding the following CE specific, must be met to maintain EMC capabilities. (see Declaration of Conformity to EC Directives)
1.
The synchronizer must be mounted against a metal ground plate with four bolts which make positive electrical connec-
tions between the case and the back plane, or backing plate PL128, available from GAC, must be installed.
2.
All cable shields on connections to the synchronizer must be connected to the case at the screw on the case as shown
on Wiring diagram.
3.
The battery minus connection to Terminal 10 must be jumpered to the case as shown in the Wiring diagram.
4.
The installer must refer to the Wiring Diagram for proper electrical connections.