Temperature indicator

Advertisement

Available languages

Available languages

Quick Links

T P 3
Temperature lndicator----------
I
INSTRUCTION MANUAL
Thank you for purchasing HANYOUNG NUX Co.,Ltd. product.
Please check whether the product you purchased is the exactly
same as you ordered . Before using this product, please read
instruction manual carefully .
Safety Information
Please read safety information carefully before using this product in order to use it
properly. Safety information described in this manual contains important contents
regarding safety. So users must follow following instructions accordingly. Safety
information is composed of WARNING and CAUTION.
&WARNING
1. Please input proper power voltage in order to prevent product to break down or get
damaged.
2. Please avoid place where inflammable or explosive gas exist. This product is not
explosion-proof construction.
3. Please tum off power before attach and detach this product. It may cause electric shock,
malfunction and break down
4.Please do not touch or conta
t the input/output terminals. It may cause electric shock
c
_&
CAUTION
1. The contents in this manual may changed without prior notice.
2. Please check whether delivered product is same as what you have asked for. (check
model name and specmcations)
3. Please check whether any parts have been damaged during delivery
4. Please avoid place where corrosive gas(especially noxious gas, ammonia and etc)
and inflammable gas exist
5. Please avoid place where vibration and impaction carry into the product directly.
6. Please avoid place where liquid, oil, medical substances, dust, salt or iron contents
exist(al.Oid place of pollution level 1 or 2)
7. Please avoid place where excessive induction trouble, static electricity or magnetic noise
occur
8. Please avoid place wtth possible thermal accumulation which caused by direct sunlight
or heat radiation.
9. Please use compensation lead wires in case of thermo couple input (using normal or
general wire will cause temperature error)
10.ln case of inputting RTD, please use small lead wire resistance and no resistant
difference within 3 wires. (temperature error occur when r
3 wires)
11. In order to al.Oid from effect of induction noise when using input signal line, avoid main
power line, power line and load line.
12.Separate input signal line and output signal line. If separating those two lines is
impossible then use shield line for input signal line.
13. For thermo couple, please use non-earthing sensor. (In case of using earthing sensor,
malfunction of device might occur due to electric leakage)
14. If there is an excessive noise from power supply, it is recommended to use insulating
transformer and noise filter. The noise filter must be attached to back side of the panel
and wire of output side filter and power supply terminal should be as short as possible.
15. Instrument power line should be arranged very closely in order to get noise efficiency
16. When connecting this device to a panel, please use a circuit breaker or switch approved
by IEC947-1 or IEC947-3.
17. Because switch or circuit breaker has been installed, please write down about
disconnection of power on a panel if switch or circutt breaker operates properly.
18. Some parts of this product have limtted l�e and others vary depending on their usage.
19. If product is properly used, warranty period is one year including parts
20. When power is ON, the preparation period of contact output is required. In case of
using signals of external interlock circuit, use a delay relay
21. In case of break down of replaced instrument, please check for compatibilfy before
replaces tt with prepared instrument. Although specifications might be same but
difference of setting parameter can cause unwanted operation.
Suffix code
Model
Code
□,□,□
5 Chanel Temperature Indicator
TP3
Only for indication
o,
Ad;Jsli' IT10Y8IT
I
K (-50-1200 •c)
K'
I
(-50-800 'C)
J
J,
Input
Pt 100 Q (-100-400 · c i
p,
100 - 240 V a.c, 50 - 60 Hz
P
I
4
Power
sistant value different among
e
Remark
Content
(CA)
(IC)
DIN Pt100 Q
1381-3, Juan-Dong, Nam-Gu lncheon, Korea
HEAD/ OFFICE
TEL: (82-32)876-4697 FAX: (82-32)876-4696
Specification
100 - 240 V a.c(±10 %), 50 - 60 Hz
Power Voltage
Below 5VA
Power Consumption
Thermo couple : K, J, R
Input
R.T.D: DIN Pt100 Q
Thermo couple : ±0.5% of displayed value + 1 Digit or ±3 ·c
(Choose bigger value).
ln case of using R input:o-199•c withi n : ±0 . 5'C
Accuracy
R.T.D: ±0.5% of displayed value ±1 digit or ±2
bigger value).
Only for indication (5 Chanel)
Control
Digital method by using selecting button ( *)
Setting method
Product
96mm x 48mm x 100mm
size
• Temperature display is automatic from channel 1 to 5 or
Other functions
temperature display of fixed channel.
• Revise temperature offset within each channel.
AmbientTemp.
Below o ·c-50 ·c /35-85 % R.H.
Humidity
Dimensions and Panel Cutout
96
�l "t: :
3.DI :
P
0 ...
-IID(
Name Of Each Parts
i r Lp3.n· c
Chamel1
C
Chamel2
Chamel3
c ..
Chamel4
Chamel5
MA0904E0B1219
l1UX
HI\JlYOlJnG
•c
(Choose
(Unit:mm)
12.5
100
Connections
Meuured Value (Red)
u.
.
Automatic Channel
AUTO
Switching Lamp(Red)
0
TP3
Selecting button

Advertisement

loading

Summary of Contents for HANYOUNG NUX TP3

  • Page 1 T P 3 Temperature lndicator---------- INSTRUCTION MANUAL Thank you for purchasing HANYOUNG NUX Co.,Ltd. product. Please check whether the product you purchased is the exactly same as you ordered . Before using this product, please read 1381-3, Juan-Dong, Nam-Gu lncheon, Korea instruction manual carefully .
  • Page 3 • 각 채널 별 온도 옵셋(Offset)교정 배선은 짧게 하여 주십시오. 0 ℃ ~ 50 ℃ / 35 ~ 85 % R.H. 이하 사용주위온· 습도 외형치수 및 접속도 ■ 각부의 명칭 ■ 접속도 (※TP3 기준) ■ 외형 및 패널 가공치수 (단위:mm)
  • Page 4 옵셋 (Offset) 교정 채널동작 설정 현재온도 표시방법 기타 상태표시...