Yearly Appliance Check And Maintenance; Variable Heat Output - Immergas VICTRIX 115 1 I Instruction Booklet And Warning

Hide thumbs Also See for VICTRIX 115 1 I:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 117
3.20 YEARLY APPLIANCE CHECK AND
MAINTENANCE.
The following checks and maintenance should
be performed at least once a year.
- Clean the flue side of the heat exchanger.
- Clean the main burner.
- Check correct ignition and functioning.
- Check correct calibration of the burner in
central heating phase.
- Check correct functioning of control and
adjustment devices and in particular:
- the intervention of main electrical switch on
the boiler;
- system regulation probes intervention;
- Check sealing efficiency of the gas circuit and
the internal system.
- Check intervention of the device against no gas
ionisation flame control:

3.21 VARIABLE HEAT OUTPUT.

HEAT
HEAT
BURNER GAS
OUTPUT
OUTPUT
FLOW RATE
(kW)
(kcal/h)
111,0
95460
108,0
92880
105,0
90300
102,0
87720
99,0
85140
96,0
82560
93,5
80446
90,0
77400
87,0
74820
84,0
72240
81,0
69660
78,0
67080
75,0
64500
72,0
61920
69,0
59340
66,0
56760
63,0
54180
60,0
51600
57,0
49020
54,0
46440
51,0
43860
48,0
41280
45,0
38700
42,0
36120
39,0
33540
36,0
30960
33,0
28380
30,0
25800
29,5
25370
N.B.: the power data in the table has been obtai-
ned with intake-exhaust pipe measuring 0.5 m
in length. Gas flow rates refer to heating values
below a temperature of 15°C and at a pressure of
1013 mbar. Burner pressure values refer to use
of gas at 15°C.
- check that the relative intervention time is less
than 10 seconds.
- Visually check for water leaks or oxidation
from/on connections and traces of condensate
residues inside the sealed chamber.
- Check, by means of the condensate drain cap,
that there are no residues of material blocking
the flow of condensate.
- Check contents of the condensate drain trap.
- Visually check that the water safety drain valve
is not blocked.
- Check that the system static pressure (with
system cold and after refilling the system by
means of the filler cock) is between 0.5 and 1.2
bar.
- Visually check that the safety and control
devices have not been tampered with and/or
shorted, in particular:
METHANE (G20)
REVS
BURNER GAS
FAN
FLOW RATE
(m
/h)
(n°)
3
11,94
5900
11,61
5720
11,29
5550
10,97
5370
10,64
5200
10,32
5030
10,06
4890
9,68
4690
9,36
4530
9,03
4370
8,71
4210
8,39
4050
8,07
3890
7,75
3740
7,43
3590
7,10
3440
6,78
3290
6,46
3140
6,14
2990
5,82
2850
5,50
2710
5,17
2570
4,85
2430
4,53
2300
4,21
2160
3,89
2030
3,56
1900
3,24
1770
3,19
1750
- temperature safety thermostat;
- Check the condition and integrity of the elec-
- electrical power cables must be inside the
- there must be no traces of blackening or bur-
N.B.: on occasion of periodical maintenance of
the appliance it is appropriate also to check and
perform maintenance on the central heating
system, in compliance with that indicated by the
regulations in force.
PROPANE (G31)
REVS
FAN
(kg/h)
(n°)
8,76
5700
8,52
5540
8,29
5370
8,05
5210
7,81
5050
7,58
4900
7,38
4770
7,10
4580
6,87
4430
6,63
4280
6,39
4130
6,16
3980
5,92
3830
5,69
3680
5,45
3540
5,21
3400
4,98
3250
4,74
3110
4,51
2970
4,27
2830
4,03
2700
3,80
2560
3,56
2420
3,33
2290
3,09
2160
2,85
2030
2,62
1900
2,38
1770
2,34
1750
trical system and in particular:
whipping;
ning.
TR
CZ
SI
RU
IE
141

Advertisement

Table of Contents
loading

Table of Contents