T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS
Symptom
Heating or cooling
Heat or cool circuit is
come on
opening up or becoming
momentarily and
high impedance.
shut off.
System on
Fan operation set for 0
indicator
(conventional heat) when it
(flame=heat,
should be set for 1 (electric
snowflake=cool)
heat).
is displayed, but
Conventional heating
no warm or cool
equipment turns on the fan
air is coming from
when the furnace has
the registers.
warmed up to a setpoint.
Heating or cooling
equipment is not operating
Outdoor
Option not activated.
temperature not
a
displayed.
Outdoor
Outdoor sensor is
temperature
connected incorrectly.
display is
Wrong sensor.
a
incorrect.
a
Select models.
69-1626
Table 6. Troubleshooting Guide.
Possible Cause
Add resistor in parallel with load or install interface relay.
Enter Installer Setup number 2 and reconfigure the fan operation.
Wait a minute after seeing the on indicator and then check the
registers.
Verify operation of heating or cooling equipment in self-test.
Enter Installer Setup number 24 and set to 1. Thermostat must have
OT terminals and a C7089B1000 installed.
Refer to C7089B1000 installation instructions and check wiring
between the thermostat and sensor.
Replace sensor with C7089B1000 sensor.