Functions - Honeywell NOTIFIER LCD6000A Installing Manual

Remote panel
Table of Contents

Advertisement

FUNCTIONS

LCD-6000A can execute the following functions:
 Local ACK
 Lamp test
 Buzzer test
 Peripheral address programming
FUNCTIONING
Needs local programming to assign peripheral address. LCD-6000A shows time, date and events previously
programmed, that come from AM series control panels.
Technical features
Microprocessor based system
LCD graphic 320 x 240 pixel display
Keyboard with dedicated keys for special functions: Buzzer silencing, Reset, Lamp Test.
Serial lines:
- 2 RS-485 interfaces
Power supply
10 ÷ 30Vdc
Connections
- 2 power cables
- 2 cables for serial line connection (3 wires if power supplies are not in common) with control panel
Mechanics
LCD-6000 mechanical features are suitable for wall-mounting
Dimensions: 180 (W) x 168 (H) x 55 (D) mm
Protection grade: IP20
Operating temperature: -5°C to +40°C