Shielded Cable And Grounding; Ldc-6000A Board Topographic - Honeywell NOTIFIER LCD6000A Installing Manual

Remote panel
Table of Contents

Advertisement

Shielded cable and grounding

During installing you need to consider
consequences of remote
grounding.
When you connect RS-485 devices, if a
ground cable (drain) is available,
this MUST NOT be connected at
both the ends to devices' chassis.
Grounding cable must be connected
ONLY to the control panel's end.
Leave the other end not connected
and insulated.

LDC-6000A board topographic

Buzzer
Linking cables technical data
Up to 1.200 m
Up to 1.500 m
PAGE - 12
NOTIFIER ITALIA
Schermo:
Connettere al
telaio con un
anello M5 e vite
Utilizzare la
posizione sul
telaio più vicina al
connettore
RS-485 shielding and grounding
CNT connector for front keyboard
18 AWG
16 AWG
Installing manual
Doc. M-185.1-LCD6000A-ENG Rev A.1
Schermo:
collegare
assieme le due
calze dei cavi
A
B
Tipico collegamento alla
centrale
Belden 9574
Belden 9575
A
B
Tipico collegamento
dell'ultima periferica
CN1 terminal board
LCD6000A
LCD6000A_manu

Advertisement

Table of Contents
loading

Table of Contents