Tech Novitas 6 User Manual page 43

Table of Contents

Advertisement

Battery
LED
flashing but
9
no
charge
voltage
and current
Buzzer beeps every
0.5
seconds
LCD display "output
10
overload"
Buzzer long beeps,
11
LCD display "output
short circuit"
The
LED
of
12
Module
with
light
The UPS only works
13
on bypass mode
14
Can not Black start
Buzzer
beeps
continuously and
15
LCD
indicates
Rectifer fault or
output fault
Tech Novitas FZC: P.O. Box 8073 Q3-144 SAIF ZONE, UAE Phone no.: +971 6 5529892
Battery
breaker
is
switch on, or batteries are
damaged,
or
reversely connected.
battery number and capacity
are not set correctly.
and
Overload
The UPS output is in short
circuit
the
The module is not inserted
RED
properly.
The UPS is set to ECO mode,
or the transfer times to bypass
mode are limited.
Battery switch is not properly
closed;
Battery fuse is not open;
Or Battery low
UPS is out of order
Tech Novitas (FAR EAST), Ltd. Hong Kong
www.technovitas.com
Switch on the battery breaker. If
does
not
batteries
replace
battery
is
Connect the battery cables correctly;
Go to LCD setting of the battery
number and capacity, set the correct
data.
remove some load
Make sure the load is not in short
circuit, then restart the UPS.
Pull out the module and insert
properly.
Set the UPS working mode to Single
Module type(non-parallel) or to reset
the times of transferring to bypass or
re-start the UPS
Close the battery switch;
Change the fuse;
Recharge the battery
for repair
- 42 -
Ain modular UPS manual
are
damaged,
whole
group
Consult with your local agent