Summary of Contents for Tech Novitas Vega KS Series
Page 1
VEGA KS ( 1/2/3 KVA ) MANUAL Publish statement Thank you for purchasing Tech Novitas VEGA KS 1/2/3 Series UPS. This series UPS is an intelligent, single phase in single phase out, high frequency online UPS designed by our R&D team who is with years of designing experiences on UPS.
Safety instructions in this manual act as a supplementary for the local safety instructions. Tech Novitas will not assume the liability caused by breach of safety instructions.
VEGA KS ( 1/2/3) KVA MANUAL easily accessible and close to the UPS system. l Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shockproof outlet). l Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
VEGA KS ( 1/2/3) KVA MANUAL l Caution - risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present! l Batteries may cause electric shock and have a high short-circuit current.
VEGA KS ( 1/2/3) KVA MANUAL 2. Installationand setup NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. 2-1 Unpack checking l Don’t tilt or reverse pack the UPS when moving it out from the packaging.
Page 7
VEGA KS ( 1/2/3) KVA MANUAL 2KVA(S/H): 3KVA(S/H):...
VEGA KS ( 1/2/3) KVA MANUAL 1. Output receptacles(10A) 2. Battery Terminal 3. SNMP intelligent slot (option) 4. Network /Fax/Modem Surge Protection(option) 5. RS-232 communication port 6. AC inputreceptacle 7. Input circuit breaker 8. EPO(option) 9. USB(option) 10. Output receptacle(16A) 2-3 Installing the UPS l Rackmount installation The Rackmount cabinet comes with all of the hardware required for installation...
Page 9
VEGA KS ( 1/2/3) KVA MANUAL Figure1Securing the Rails Select the proper size in the rack for positioning the UPS (see Figure 2). The railoccupies four positions on the front and rear of the rack. Tighten four M5 Umbrella Nuts in the side of rail assembly(see Figure 1). Fix one rail assembly to the front of the rack with one M5×12 pan-head screw and one M5 cage nut.
Page 10
VEGA KS ( 1/2/3) KVA MANUAL If installing optional cabinets, repeat Step 8 and 9 for each cabinet. Slide the UPS and any other optional cabinets into the rack. Secure the front of the UPS to the rack using one M5×12 pan-head screws and one M5 cage nuts on each side(see Figure 4).Install the bottom screw on each side through the bottom hole of mounting bracket and the bottom hole of the rail.
Page 11
VEGA KS ( 1/2/3) KVA MANUAL Figure5Extract UPS front cover CAUTION A small amount of arcing may occur when connecting the internal batteries. This is normal and will not harm personnel. Connect the cables quickly and firmly b) Connect the internal battery connector(see Figure6) Connect red to red, Press the connector tightly together to ensure a proper connection.
Page 12
VEGA KS ( 1/2/3) KVA MANUAL d) Replace the UPS front cover. To replace the cover, verify that the ribbon cable is protected and (ifEBPS are installed) the EBP cable is routed through the knockouton the bottom of the cover. Put the front cover hooks of side with display to the cover port, put another side to the other two ports, then press it until the cover and the chassis are combined tightly.
Page 13
VEGA KS ( 1/2/3) KVA MANUAL It is the same with the installation of the front cover. (Refer” To install the UPS“) Figure8Removing the EBP Front Cover b) On the bottom of the UPS front cover, remove the EBP cableknockout (see Figure Figure9Removing the UPS Cable Knockout c) For the bottom (or only) EBP, remove the EBP cable knockout on the top of the EBP front cover.
Page 14
VEGA KS ( 1/2/3) KVA MANUAL four EBPS may be connected to the UPS.Connect black to black,. Press the connector tightly together to ensure a properconnection. To connect a second EBP, unclip the EBP connector onthe first EBP and pull gently to extend the wiring to the EBPconnector on the second EBP.
Page 15
VEGA KS ( 1/2/3) KVA MANUAL Figure 11 plasticbase installation ③ If anEBP is needed to be placed in the middle, the assembly of plastic base is similar(Figure 11 ).The difference is that two 1U plastic base extended boards are added in the middle.(as the following shows) (A)...
Page 16
VEGA KS ( 1/2/3) KVA MANUAL (E) (F) Figure 12increase EBP plasticbase installation l The installation between UPS and EBPS can be referred to Fig.13 Figure13The installation for UPS and battery box Figure14 Long backup external battery connection a) Install the base, then place the RT UPS on the base one by one as Fig.13 shows.
VEGA KS ( 1/2/3) KVA MANUAL b) The cover installation and cable connection of the UPS and EBPS are the same as RT. (To install the optional EBP(s) for a UPS) 2-4 UPSstartup and turn off l Startup operation (1) Turn on the UPS in line mode NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm.
VEGA KS ( 1/2/3) KVA MANUAL a) Press and hold the OFF key for more than half a second to turn off the UPS. b) When turning off the UPS, it will do self-testing firstly. The LEDs light and go out circularly and orderly until there is no display on the cover.
VEGA KS ( 1/2/3) KVA MANUAL LCD control panel introduction (1)LED(fromtop to bottom: “alarm”, “bypass”, “battery”, “inverter”); (2)On-Line UPS LCD display;(3)Buttons-FUNC button/OFFbutton/On button. Status Indicator Description The UPS has an active alarm or fault. The UPS is in Bypass mode. The UPS is operating normally onbypassduring High Efficiency operation.
Page 20
VEGA KS ( 1/2/3) KVA MANUAL configuration: a) Remove the small cover of the terminal block b) Suggest using AWG14 2.1mm power cords 3KVA (200/208/220/230/240VAC models). c) Upon completion of the wiring configuration, please check whether the wires are securely affixed. d) Put the small cover back to the rear panel.
VEGA KS ( 1/2/3) KVA MANUAL 3. Operations 3-1 Button operation Button Function Turn on the UPS: Press and hold ON button for Ø at least 2 seconds to turn on the UPS. Choosing different value: When the UPS Ø entersthe setting mode, press this button to ON Button choose the different value what you want.
VEGA KS ( 1/2/3) KVA MANUAL be ineffective when the input voltage is out of acceptable range. Switch LCD message: Press this button to Ø change the LCD message for input voltage, input frequency, battery voltage, output voltage and output frequency etc. Rotate Key:After the UPS turn on, continue to Ø...
Page 23
VEGA KS ( 1/2/3) KVA MANUAL Input voltage Battery voltage Output voltage Load...
Page 24
VEGA KS ( 1/2/3) KVA MANUAL Environment Temperature Firmware Version & UPS model CODE (Operational status and mode) Alarm Code(Warming Message) All alarm codes are present when abnormal behavior(s) occur(s) Part two: Tower display...
Page 25
VEGA KS ( 1/2/3) KVA MANUAL ●After the UPS turn ON, continue to press the function key for 10 seconds , the LCD screen begin to rotate. ●LCD display with rotation function and after rotating display information content is constant ,the LCD display information only display the direction and pattern of change. ●LCD display after rotation, and then shut down, to boot, the LCD screen saved with rotating state .
Page 26
VEGA KS ( 1/2/3) KVA MANUAL Load Environment Temperature Firmware Version & UPS model...
Page 27
VEGA KS ( 1/2/3) KVA MANUAL CODE (Operational status and mode) Alarm Code(Warming Message) All alarm codes are present when abnormal behavior(s) occur(s) The charging status can also be shown on the screen as below while the charger is on. Cc MODE...
VEGA KS ( 1/2/3) KVA MANUAL Cv MODE 3-3 UPS setting TheUPS has setting functions. This user settings can be done under any kind of UPS working mode. The setting will take effect under certain condition. Below table describes how to set the UPS. The setting functioniscontrolled by 3 buttons (FUNC/Up▲,OFF/Down▼, ON/EnterP): FUNC/Up ▲+OFF/Down▼---goes into the setting page, ON/Enter P--- value adjustment;...
Page 29
VEGA KS ( 1/2/3) KVA MANUAL Output voltage setting Press Enter button P to change thesetting(100,110,115,120,127 or 200,208,220, 230, 240). Press UP button ▲ to select the previous setting. Press DOWN button▼to select the next setting. Frequency setting Press Enter button P to change the setting (50 or 60Hz).
Page 30
VEGA KS ( 1/2/3) KVA MANUAL Bypass voltage upper limit setting Press Enter button P to change the setting(The bypass voltage upper limit range is 230-264Vac ). Press UP button ▲ to select the previous setting. Press DOWN button ▼ to select the next setting.
VEGA KS ( 1/2/3) KVA MANUAL BYPASS enable/disable setting Press Enter buttonP to change thesetting(ON or OFF). Press UP button ▲ to select the previous setting. Press DOWN button ▼ to save and exit the setup. 3-4 Operating Mode Description Mode Description Indicator...
VEGA KS ( 1/2/3) KVA MANUAL The bypass yellow LED is on. Bypass tolerance can be set by Bypass voltage limit setting. Under below conditions, the UPS will transfer to bypass mode: Bypass ●BPS on set by user through Mode setting Mode , and set to ECO Mode.
VEGA KS ( 1/2/3) KVA MANUAL Output Short-circuit Once per second Fault LED blinking Input current limit Once per second Fault LED blinking Bypass over current Once per second BPS LED blinking INV or BPS LED Overload Once per second blinking No battery Once per second...
Page 35
VEGA KS ( 1/2/3) KVA MANUAL Alarm code is shown as Battery voltage is too “34” and battery led Contact your dealer. low or the charger is blinking fault. Alarm code is shown as UPS is overload Remove excess loads from “32”...
Page 36
VEGA KS ( 1/2/3) KVA MANUAL C heck t he w i r e R ef eR t o W i r i ng connect r ef er t o D i agr am w i r i ng D i agr am C heck t he U PS m ode( I nput vol t age B at vol t age) U PS t ur n on...
VEGA KS ( 1/2/3) KVA MANUAL Trouble Shooting Chart 5. Storage and Maintenance l Operation The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
VEGA KS ( 1/2/3) KVA MANUAL Specification MODEL 1KVA(S) 1KVA(H) 2KVA(S) 2KVA(H) 3KVA(S) 3KVA(H) PHASE Single phase with ground Capacity (VA/Watts) 1000VA / 900W 2000VA / 1800W 3000VA / 2700W INPUT Nominal voltage 200/208/220/230/240VAC 160Vac±5% @100%-80% load; 140Vac±5% @80%-70% load; Low line 120Vac±5% @70%-60% load;...
Page 39
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 Product specifications are subject to change without further notice. Mail Us at info@technovitas.com / support@technovitas.com Tech Novitas FZC: P.O. Box No.:8073, Q3-144 SAIF ZONE, U.A.E. Phone No.: +971 6 5529892 Tech Novitas (Far East) Ltd. Hong Kong. www.technovitas.com...