Chamberlain 50-HERK2 Manual

Chamberlain 50-HERK2 Manual

Microwave motion sensor for commercial doors

Advertisement

Quick Links

INTRODUCTION
The 50-HERK2 is an advanced planar microwave motion sensor designed
for commercial doors and gates. The sensor can differentiate between
people and vehicles. Its two relay outputs can be programmed
independently for a multitude of applications. Additional features include
cross-traffic optimization and slow-motion detection.
CARTON INVENTORY
50-HERK2 sensor with pre-wired 23' (7 m) 6-wire cable
Self-adhesive mounting template
Instructions
TOOLS AND HARDWARE NEEDED
Ladder
Tape measure
Level
Drill with 3/16" or 5 mm bit
3/16" or 5 mm mounting screws (2)
Screwdriver
4 AWG (5 mm diameter) wire stripper for cable sleeve
24 AWG (0.5 mm diameter) wire stripper for single wires
Other items recommended for installation:
Remote control (Model 50-HERK-RC2)
OVERVIEW
Mounting bracket
Inclination angle
hand-screws (2)
Cable
Clip for wide field sensing
Microwave planar module
50-HERK-RC2 remote control (not provided)
Required to access complete set of functions
for remote setup and operation
MICROWAVE MOTION SENSOR
for Commercial Doors
Failure to follow these safety precautions may cause DAMAGE to
sensor or objects, SERIOUS PERSONAL INJURY, or DEATH.
• This product is designed to be mounted above an overhead
commercial door.
• DO NOT use this product other than for its specified application.
• Observe ALL applicable local, national, and international door safety
standards, codes, and laws.
• ONLY trained and qualified personnel may install and initialize the
sensor.
• ONLY authorized factory personnel may perform hardware/software
changes or repairs to the product.
• The sensor should ONLY be operated from a safety extra low
voltage (SELV) system with safe electrical separation.
• ALWAYS consider the safety functions of your applications as a
whole, NEVER just in relation to one individual section of the
system.
• The installer is responsible for testing the system to ensure it
meets ALL applicable safety standards (e.g. UL 325).
• NEVER touch ANY electronic components or lenses.
• After accessing the inside of the sensor, ensure the cover/
protection seal is closed tightly to achieve designated protection
rating.
• ENSURE the commercial door operator has ALL of its monitored
entrapment protection devices installed and operational. This
sensor does NOT replace any entrapment protection devices.
Aluminum housing
DIP switches
Output 2 indicator (red LED)
Output 1 indicator (green LED)
R
Right button
L
Left button
MODEL 50-HERK2
Front cover
Cover screws (4)

Advertisement

Table of Contents
loading

Summary of Contents for Chamberlain 50-HERK2

  • Page 1 Commercial Doors MODEL 50-HERK2 INTRODUCTION The 50-HERK2 is an advanced planar microwave motion sensor designed for commercial doors and gates. The sensor can differentiate between Failure to follow these safety precautions may cause DAMAGE to people and vehicles. Its two relay outputs can be programmed sensor or objects, SERIOUS PERSONAL INJURY, or DEATH.
  • Page 2: Specifications

    SPECIFICATIONS Technology ... . . Doppler radar with planar module: 24.05 - Temperature range ..-22° to 140° F ( -30° to 60° C) - 0% to 95% 24.25 GHz, <20 dBm relative humidity, no condensation Detection Speed .
  • Page 3: Inclination Angle

    ADJUSTMENT INCLINATION ANGLE TILT ANGLE It may be necessary to tilt the sensor for certain applications (not After installation, adjust the inclination angle to the desired detection pattern. Adjust the inclination angle by loosening the hand-screws on the recommended unless warranted by special circumstances). Loosen the sides of the sensor and adjusting as shown below.
  • Page 4: Sensor Functions

    PROGRAMMING - WITHOUT REMOTE CONTROL SENSOR FUNCTIONS Several crucial functions can be programmed with the buttons on the sensor. All remaining functions must be configured by the 50-HERK-RC2 remote control (not provided). 1. Remove the screws from the front cover and remove the front cover to locate the LEFT L and RIGHT R buttons.
  • Page 5: Remote Control Power

    PROGRAMMING - WITHOUT REMOTE CONTROL WIDE FIELD SENSING To use wide field sensing, the clip MUST be installed on the front of the microwave planar module and the wide field setting turned to ON. The sensor will not function correctly if the clip is installed and the wide field setting is set to OFF. The wide field setting is only available for mounting heights up to 13' (4 m).
  • Page 6 PROGRAMMING - WITH REMOTE CONTROL (NOT PROVIDED) If unable to enter programming mode with the remote control or no access code is set, use one of the alternate methods: Enter programming mode (OPTION 2): Restart the sensor (temporarily disconnect the power supply). Programming mode is activated when the sensor is switched on. Enter programming mode (OPTION 3): Remove the screws from the front cover and remove the front cover.
  • Page 7 PROGRAMMING - WITH REMOTE CONTROL (NOT PROVIDED) SENSOR FUNCTION REMOTE VALUES DESCRIPTION CONTROL FUNCTION NO (Normally Opened) * Output 1 and 2 factory default F3 (Output 1) Logic NC (Normally Closed) F4 (Output 2) OFF - Door always activates when any * Factory Default crossing traffic is detected.
  • Page 8: Troubleshooting

    TROUBLESHOOTING SYMPTOM SOLUTION People/vehicle separation does not work as expected Check mounting height and setting (more than 10' [3 m] is recommended) Check mounting situation and environment (sensor centered above door is best) Check setting/clip for wide field pattern Late detection of traffic Increase field size/sensitivity Adjust inclination angle to move the pattern away from the door Door reverses (sensor reacts to closing door)

This manual is also suitable for:

50-herk-rc2

Table of Contents