Download Print this page

Ziton ZP2-ZI Installation Sheet page 2

Zone led indicator
Hide thumbs Also See for ZP2-ZI:

Advertisement

EN: Installation Sheet
Description
The Zone LED Indicator is an expansion board for fire and
repeater panels. It shows the status of selected zones. Model
numbers and capacities are given in Table 1.
Table 1: ZP2-ZI Zone LED Indicators
Product
Number of zones
ZP2-ZI-20
20 zones
ZP2-ZI-40
40 zones
ZP2-ZI-24
24 zones
The zone LED indicator shows the status of up to 20 or 40
zones in a large fire panel or repeater control panel, and up to
24 zones in a small fire panel. The LED indicator uses two
LEDs per zone to indicate zone events and status.
The red LED indicates an alarm in the corresponding zone:
A flashing red LED indicates a detector (or automatic) fire
alarm
A steady red LED indicates a manual call point fire alarm
The yellow LED indicates a fault, test, or disablement in the
corresponding zone:
A flashing yellow LED indicates a fault
A steady yellow LED indicates that the zone is disabled or
is being tested
Installation
WARNING:
To avoid personal injury or death from
electrocution, disconnect the control panel from the mains
power supply and batteries before installing this product.
To install the zone indicator:
1.
Unscrew and remove the plastic cover from the inside of
the control panel door.
2.
Install the zone indicator inside the control panel door, as
shown in Figure 1 for the large panel, or Figure 5 for the
small panel. Secure the board using the screws provided.
3.
Restore power and add the zone indicator to the control
panel configuration. (See the control panel installation
manual for further details.)
4.
Use the supplied inserts to label each zone.
For a 20- or 40-zone indicator, label the inserts as shown in
Figure 3 or Figure 4. Slide the insert into the appropriate slot
as shown in Figure 2.
For a 24-zone indicator label the inserts as shown in Figure
Slide the insert into the appropriate slot as shown in Figure 6.
www.acornfiresecurity.com
Compatible panel
Large panel
Large panel
Small panel
7.
www.acornfiresecurity.com
Specifications
Maximum number of zones
ZP2-ZI-20
ZP2-ZI-40
ZP2-ZI-24
Typical current consumption (active) [1]
ZP2-ZI-20
ZP2-ZI-40
ZP2-ZI-24
Typical current consumption (standby) [2]
Weight
ZP2-ZI-20
ZP2-ZI-40
ZP2-ZI-24
Dimensions (W × H)
ZP2-ZI-20
ZP2-ZI-40
ZP2-ZI-24
Temperature
Operation
Storage
Relative humidity
[1] All LEDs on
[2] All LEDs off
Regulatory information
Certification
Manufacturer
UTC CCS Manufacturing Polska Sp. Z o.o.
Ul. Kolejowa 24, 39-100 Ropczyce, Poland.
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands.
Year of first CE
11
marking
20
40
24
12 mA at 24 VDC
14 mA at 24 VDC
12 mA at 24 VDC
2.2 mA at 24 VDC
135 g
140 g
50 g
267 x 152 mm
267 x 152 mm
267 x 63 mm
–5 to +40°C
–20 to +50°C
10 to 95% noncondensing

Advertisement

loading

This manual is also suitable for:

Zp2-zi-20Zp2-zi-40Zp2-zi-24