LK Systems PE-X Assembly Instructions Manual page 7

Pipes
Table of Contents

Advertisement

Pipe installation in concrete structures
In concrete structures, conduits may be clamped
to reinforcements using cable ties or similar. The
distance between the attachment points should
not exceed 1 m to prevent the risk of the pipes
moving up during casting. The cable ties must
not be tightened excessively in a manner that
would deform or damage the conduit. When us-
ing LK PE-X pipes for concealed Pipe-in-Pipe lay-
ing in concrete, it is extremely important to con-
sider expansion-absorbing devices.
If the pipes are not laid with sufficient enough
room to expand, radiators/mixers may come
loose from their brackets in the event of high
temperature differences between the time of in-
stallation and when the system becomes fully op-
erational. Pipe expansion may also occur at mani-
folds, leading to a risk of the pipes coming loose
from their couplings. Ensure that the PE-X pipes
are pulled up into the couplings to the manifolds
or radiators/mixers in order to provide space for
expansion in the conduit/sleeve pipe. No expan-
sion-absorbing devices are needed for concealed
laying of "naked" LK PE-X and LK PAL pipes in
concrete as the pipes are secured in position in
the concrete.
Example of expansion-absorbing bends for concealed lay-
ing of Pipe-in-Pipe.
If underfloor heating is installed in the concrete
slab, the tapwater pipes must be placed at least 100
mm beneath the top edge of the topmost layer of
insulation. Alternatively, Pipe-in-Pipe Extra (insu-
lated pipes) may be laid beneath the insulation.
Tap water pipes and hot water circulation pipes
which are installed in concrete constructions with-
out floor heating should be placed in the insulation
or alternatively as Pipe-in-Pipe Extra above the
insulation.
Assembly instructions | LK PE-X, PAL and PE-RT pipes
Lashing
against reinforcement
at a maximum distance of 1 m.
Clamping against reinforcement.
Laying of Pipe-in-Pipe in a concrete slab with underfloor
heating.
Pipe laying using LK PE-X
and LK PAL to kitchen faucet
Dish washer
connection
Acceptable solution when installing kitchen mixers with
copper connecting pipes with LK PE-X and PAL Universal
pipes Pipe-in-Pipe.
Concrete
Reinforcement
LK Clip Rail
LK Underfloor Heating Pipe
Insulation
Pipe-in-Pipe
Pipe-in-Pipe Extra
Copper pipes
LK PE-X and PAL Universal pipe
Expansion space
EN.29.C.41.191217
7 (10)

Advertisement

Table of Contents
loading

This manual is also suitable for:

PalPe-rt

Table of Contents