Pipe properties

Designation
Pipe
dim.
(mm)
LK Under Floor
8x1.0
Heating Pipe
12x2.0
LK Under Floor
16x2.0
Heating Pipe
20x2.0
LK Heating pipe
25x2.3
32x2.9
LK Universal
16x2.0
Pipe PE-X
20x2.5
25x3.5
LK Universal
16x2.0
Pipe PAL
20x2.5
25x3.5
32x3.0
40x3.5
50x4.0
63x4.5
75x7.5
LK Pal Universal Pipe A16 (16x2,0) 10 bar 95°C Oxygen barrier acc. to DIN 4726 Certification body Date Time Metre
Example of markings for identification of a pipe

Marking and identification

LK pipes can always be identified as they are
marked repeatedly at every metre.

Bending

Bending of LK PE-X and PE-RT
Minimum recommended bend radii:
Bending method
Cold bending without fixture
Cold bending with fixture
Hot bending with bending
support
Precautions must be taken when installing PE-X
and PE-RT pipes at temperatures below -5 ˚C, par-
ticularly when bending.
EN.29.C.41.191217
2 (10)
Material
Pipe range, design
Except
PiP
PiP
con-
Extra
duit
PE-Xa
X
PE-RT
X
PE-Xa
X
PE-Xa
X
X
X
PE-RT/
X
X
X
AI/
X
X
X
PE-RT
X
X
X
X
X
X
X
X
X
X
Minimum bend radius at
pipe dim.
16
20
25
32
80
130
180
260
55
110
140
210
34
45
60
95
Pres-
Temperature range
sure
class
Insula-
Max.
tion
con-
tinuous
tempera-
ture
PN6
70 °C
PN6
60 °C
PN6
70 °C
PN10
70 °C
X
PN10
70 °C
X
X
X
Cold bending without fixture
Where space permits large bend radii, we recom-
mend that the pipe bends be formed without a
fixture/support. Large radii facilitate any re-
placement of the pipe in inner pipe (pipe-in-pipe)
without causing structural damage. See section
Replacement of pipes in conduits.
NOTE!
The instructions concerning clamping and fix-
ing in the section entitled Pipe laying in tim-
ber frames on page 5 must be followed for
pipes in inner pipes that are to be replaced.
Bending PE-X pipes directly after press fitting
is not recommended. The distance between
the coupling and the PE-X pipe should be a 1
x the pipe's diameter before the bending, at a
minimum. This instruction is provided due to
the risk of stress corrosion.
Standard
Max. mo-
Mini-
mentary
mum
tempera-
permit-
ture
ted
tem-
pera-
ture
95 °C
-20 °C
EN ISO 15875
(DIN16892/3)
70 °C
-20 °C
EN ISO 22391
(DIN16833/4)
95 °C
-20 °C
EN ISO 15875
(DIN16892/3)
95 °C
-20 °C
EN ISO 15875
(DIN16892/3)
95 °C
-20 °C
EN ISO 15875
(DIN16892/3)