TECHNICAL ADVISORY BULLETIN
Recommended Grounding for SE41 Remote Power Node Enclosure
Date: 4/21/2020
Model #:
SE41 Remote Power Node Enclosure
Issue
As there are three different configurations of the SE41 RPN enclosure, additional information on
grounding is required beyond what is provided in the installation manual.
Corrective Action
Provide grounding instructions with diagrams for the three different configurations of the SE41 RPN
enclosure.
The grounding specifications and diagrams depicted in this TAB are based on recommended
industry best practices. However, site grounding design and construction shall always adhere to
local electrical codes and the internal standards of the company that is responsible for ownership
and operation of equipment.
Warning
Only qualified personal should install and connect the power components within the Alpha
system.
An enclosure that is not properly grounded presents an electrical hazard and will likely result in
premature equipment failure.
A proper grounding system (i.e. ground electrode system) that meets or exceeds the
specifications of the equipment must be designed and installed prior to or in conjunction with
the installation. The ground system must be bonded to the enclosure to ensure a "common" or
"single-point" ground.
For more information visit www.alpha.com
Copyright © 2019 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies.
Other product names mentioned in this document may be registered in certain jurisdictions. Information is subject to change without notice.
Page 1 of 6
0470453-TAB Rev A (04/2020)
F-MKT-04 Rev 1.4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Alpha SE41 and is the answer not in the manual?

Questions and answers

Summary of Contents for EnerSys Alpha SE41

  • Page 1 TECHNICAL ADVISORY BULLETIN Recommended Grounding for SE41 Remote Power Node Enclosure Date: 4/21/2020 Model #: SE41 Remote Power Node Enclosure Issue • As there are three different configurations of the SE41 RPN enclosure, additional information on grounding is required beyond what is provided in the installation manual. Corrective Action •...
  • Page 2 Configuration 1: Recommended grounding of SE41 RPN with combination meter and load center Install a #2AWG tinned solid copper site ground wire (grounding electrode conductor) originating at the closest driven ground electrode and connect it to the Load Center AC Equipment Ground (ACEG) bus (refer to Figure 1).
  • Page 3 Configuration 2: Recommended Grounding of SE41 RPN with Remote AC Service Disconnect located within four feet of the SE41 cabinet Objective: Install a continuous length of #2AWG tinned solid copper conductor originating at the ACEG bus in the remote service disconnect enclosure and have it terminated at the Enclosure Master Ground Bar (MGB). Steps: Connect the #2AWG tinned solid copper conductor to the ACEG bus in the remote service disconnect enclosure and then to the ground rod nearest to the Enclosure MGB.
  • Page 4 Configuration 3: Recommended Grounding of SE41 RPN with Remote AC Service Disconnect located greater than four feet away from the SE41 cabinet Objective: Install a continuous length of #2AWG tinned solid copper conductor originating at the ACEG bus in the remote service disconnect enclosure and have it terminated at the Enclosure Master Ground Bar (MGB).
  • Page 5 Internal Wiring configurations of Enclosure Master Ground Bar Confirguation 1: Typical internal wiring of the SE41 RPN Enclosure Master Ground Bar Figure 4 – Newer versions of the SE41 RPN Enclosure Master Ground Bar Typical Wiring Configuration 2: Typical internal wiring of previous versions of the SE41 Enclosure Master Ground Bar Figure 5 –...
  • Page 6 For additional assistance or if you have any questions regarding this notification, please contact Alpha Technical Support at 1-888-462-7487 or www.alpha.ca/report-a-problem. Sincerely, Satheesh Hariharan David Veraguth Sr. Product Manager, Outside Plant Solutions Sr. Technical Support Representative Alpha Technologies Ltd. Alpha Technologies Ltd. Satheesh.Hariharan@alpha.ca David.Veraguth@alpha.ca For assistance, contact Alpha Technical Support:...

Table of Contents