WIRING CONNECTION
24
CAUTION
!
The power cord connected to the outdoor unit should be complied withIEC 60245 or HD
22.4 S4 (This equipment shall be provided with a cord set complying with the national reg-
ulation.
1 Phase(Ø)
3 Phase(Ø)
The connecting cable connected to the outdoor unit should be complied with IEC 60245 or
HD 22.4 S4 (This equipment shall be provided with a cord set complying with the national
regulation.)
When the connection line between the indoor unit and outdooor unit is over 40m, connect
the telecommunication line and power line separately.
If the supply cord is damaged, it must be replaced by a special cord or assembly availible
from the manufacturer of its service agent.
NORMAL CROSS-SECTIONAL AREA
Model
Phase(Ø)
UU85W
3
NORMAL
CROSS-SECTIONAL
AREA 1.0mm
2
2
Area(mm
)
2.5