5.0 Product Specifications
5.0
Product Specifications
Table 4. Technical Specifications
Electrical
Voltage
Total Load Current
Input Busses
Alarm Contacts
AIC
Mechanical
Dimensions L x H x D
Weight
Mounting Orientation
Environmental
Operating Temperature
Humidity
Elevation
Table 5. Agency Certifications
UL
UL File Number
UL Standard
6.0

6.0 Models and Accessories

Models and Accessories
Table 6. Model Configurations
DESCRIPTION
DCX LP; 1200A Breaker; Low Profile DC Battery Disconnect System for Unigy II 6AVR125-
33 NEBS
DCX LP; 1200A Breaker; Low Profile DC Battery Disconnect System for Unigy II 6AVR125-
33 NEBS; Switch Version
12
-40V to -60VDC
1200A
Single
Form-C, 60VDC @ 0.5A max
25,000A
41 in. x 12 in. x 20 in.
95 lbs.
Top of battery stack
0 to 50°C
0 to 95% RH non-condensing
-500 to 2800m
E473904
ANSI/UL 60950-1
PART NUMBER
C016-1540-10
C016-1545-10
C048-720-30 Rev. B (03/2021)

Advertisement

Table of Contents
loading

This manual is also suitable for:

C016-1540-10C016-1545-10