Rheem RTGH-C95DVLN Installation Instructions Manual page 24

Common venting
Hide thumbs Also See for RTGH-C95DVLN:
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS
Vertical Vent Installation
WARNING:
Improper vent installation can result in death, personal
injury, product damage, and/or poor performance.
NOTICE:
Only Rheem-approved AND ULC S636 approved termination
and parts must be used during installation.
Maintain the recommended air space clearance to
combustible materials and building insulation.
Through Roof
1
Cut a hole through the roof and interior ceiling to
accommodate the vent pipes.
2
Support vertical and horizontal runs as described in
"Common Venting". Vertical supports are required every
4 ft. (1.2 m) along a vertical pipe route, before every
transition to vertical, and after every offset elbow.
24
Hole
C L
Hole
C L
Through Ceiling
Exhaust Pipe Needs to
Have 3° Upward Slope
Toward Outdoor
NOTICE:
Free-standing vent pipe that penetrates a roof/ceiling
requires another means of support from a second location.
A, B
3
Determine the vent terminal height and install the
vent pipe accordingly. Refer to "Vertical Vent Terminal
Location" for clearance requirements.
4
Install adequate flashing where the vent pipe passes
through the roof.