Rheem RTGH-C95DVLN Installation Instructions Manual page 17

Common venting
Hide thumbs Also See for RTGH-C95DVLN:
Table of Contents

Advertisement

DO NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. To do so may result in an
explosion or fire.
This water heater can use room air for combustion and ventilation as long as the installation complies with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, and other applicable standards and local codes. Failure to comply with these standards and other instructions on
the Common Vent Installation Instructions and the Tankless Water Heater Use and Care Manual may result in death or serious injury and/or
damage to property.
X AIR SUPPLY INLET
V VENT TERMINAL
Horizontal Vent Terminal Location for Power Vent (Room Air Application)
The following information should be used for determining the proper location of the vent terminal for direct vent water
heaters.
A= Clearance above grade, veranda, porch,
deck or balcony.
B= Clearance to window or door that may
be opened.
C= Clearance to permanently closed
window.
D= Vertical Clearance to ventilated soffit located
above the terminal within a horizontal distance
of 2 feet (61 cm) from the center line of the
terminal.
E= Clearance to unventilated soffit.
F= Clearance to outside corner.
G= Clearance to inside corner.
H = Clearance to each side of center line
extended meter/regulator assembly.
I = Clearance to service regulator vent
outlet.
J = Clearance to nonmechanical air supply
inlet to building or the combustion air
inlet to any other appliance..
K = Clearance to mechanical air supply
inlet.
L = Clearance above paved sidewalk or paved
driveway located on public property.
M = Clearance under veranda, porch, deck
or balcony.
1 In accordance with current CAN/CSA-B149.1 Installation Codes.
2 In accordance with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code.
+ A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family
dwellings and serves both dwellings.
*
"Clearance in accordance with local installation codes and the requirements of the gas supplier."
INSTALLATION INSTRUCTIONS
FOR YOUR SAFETY
Inside
corner detail
Fixed
closed
Operable
Fixed
closed
Operable
AREA WHERE TERMINAL IS NOT PERMITTED
Canadian Installations
1
12 inches (30 cm)
6 inches (15 cm) for appliances < 10,000 Btuh (3
kW), 12 inches (30 cm) for appliances > 10,000 Btuh
(3kW) and < 100,000 Btuh (30kW), 36 inches (91
cm) for appliances > 100,000 Btuh (30kW).
*
*
*
*
*
*
Above a regulator within 3 feet (91 cm) horizontally of
the vertical center line of the regulator vent outlet to a
maximum vertical distance of 15 feet (4.5 m).
6 inches (15 cm) for appliances < 10,000 Btuh (3
kW), 12 inches (30 cm) for appliances > 10,000 Btuh
(3kW) and < 100,000 Btuh (30kW), 36 inches (91
cm) for appliances > 100,000 Btuh (30kW).
6 feet (1.83 m)
7 feet (2.13 m)+
12 inches (30 cm)
US Installations
2
12 inches (30 cm)
4 feet (1.2 m) below or to side of
opening; 1 foot (300 mm) above
opening.
*
*
*
*
*
*
*
4 feet (1.2 m) below or to side of
opening; 1 foot (300 mm) above
opening.
3 feet (91 cm) above if within 10
feet (3 m) horizontally.
7 feet (2.13 m)+
*
17