Siemens OpenAir GCA Series Technical Instructions page 16

Electronic damper actuators
Hide thumbs Also See for OpenAir GCA Series:
Table of Contents

Advertisement

Technical Instructions
Document No. 155-173P25
May 19, 2014
GCA15x.1x
(0 to 10 Vdc or
2 to 10 Vdc)
for Tandem
Application
(Master/Slave)
Page 16
Figure 22. Tandem Application DIP Switch Settings.
After setting the 4th DIP switch for TM (tandem mount) on all actuators
used in the tandem application, one actuator must be identified as the
Master by selecting the "M" on the 5th DIP switch.
The rest of the actuators used in the application must have the "S"
(slave) set on the 5th DIP switch.
Connect all the 2 (black) Neutral wires and connect them to the power
supply.
Connect all the 1 (red) Supply wires together and connect them to the
power supply.
The Output Signal 9 (pink) wire, identified as the Master actuator, needs
to be connected to all the Control Signal Wires 8 (gray) of the slave
actuators used in the tandem application.