Nominal Voltage
24 VAC
Temperature Display Range 0...55°C [ <0°C : LO, >55°C : HI ]
Sensing Element & Control
NTC Thermistor, 100k ohm @ 25°C
System Switch
On/Off, Cooling/Heating
Fan Control Switch
High-Med-Low or Auto-speed
LCD Display
0.5 K increase/decrease
Setpoint Range
5...35°C
Body Material
Fire-retardant ABS
Electrical Ratings
Relay output contact 2A Resistive, 1A Inductive,
Fan switch
Control Signal
On/Off Control, 3-wires & spring return 2 wires
Cooling or Heating (2-pipe system)
Temperature Range
Operating: 0 to 45°C
Storage: 0 to 50°C
Protection Class
II
Wiring Connections
Terminal wiring 0.5 ... 1.5 mm2
Agency Approval
LV Directive
EMC
Ambient Humidity
max. 95% r.h., non-condensing
Weight
140 g
Dimensions (L x H x D)
86 x 86 x 14 (mm)
Degree of Protection
IP 30
List Price
EXT-CF24-D202-AF
EXT-CF24-D402-AF
800-543-9038 USA
24 VAC 50/60 Hz
2A Resistive, 1A Inductive,
24 VAC 50/60 Hz
CE according to 2006/95/EC
CE according to 2004/108/EC
$90.00
$100.00
Overview of Functions
Slim type EXT-CF24-D202-AF and EXT-CF24-D402-AF thermostat provides the
foundation for modern fancoil applications.
Features
• Large LCD with blue backlight
• Stylish appearance with hidden buttons
• For 2 or 3 wires on-off controlled devices in 2-pipe FCU system (EXT-CF24-D202-
AF)
• For 2 wires on-off controlled devices in 4-pipe FCU system (EXT-CF24-D402-AF)
• 3 speed / auto-speed for fan controls
• Defrost - low temperature protection
• Temperature off-set adjustment
• Temperature / setpoint display selection
• Memory rentention
• Set point range adjustment
Basic Features
Modes
On/Off - Cooling
Fan speed
3 speed ( Low
Auto speed: difference between setpoint and ambient temperature,
1 K - Low
Defrost
Low temperature protection. When the unit in "OFF" status and
ambient temperature lower than 5°C, it will switch on automatically
in heat mode with "
7°C, it will stop automatically.
Backlight
The backlight will light up 7 seconds whenever button is pressed.
By pressing "
Valve
When the valve is opening, the icon "
Restart
When "RST" button is pressed, the thermostat will restart with last
saved setting.
Memory
All last saved parameters will be kept after power failure or power off.
Dimension and Terminals
866-805-7089 CANADA
LCD Electronic Thermostat
EXT-CF24-D202-AF, EXT-CF24-D402-AF
/ Heating
, Medium
, High
) / Auto
; 2 K - Medium
; 3 K - High
" showing. When the temperature reached
", backlight light up 30 seconds.
" displays.
24 VAC Neutral N (comm)
Output for fan - High speed
Output for fan - Medium speed
Output for fan - Low speed
Output for actuator - Cool
Output for actuator - Heat
24 VAC Live L
203-791-8396 LATIN AMERICA / CARIBBEAN

Advertisement

loading

Summary of Contents for Belimo EXT-CF24-D202-AF

  • Page 1 LCD Electronic Thermostat EXT-CF24-D202-AF, EXT-CF24-D402-AF Overview of Functions Slim type EXT-CF24-D202-AF and EXT-CF24-D402-AF thermostat provides the foundation for modern fancoil applications. Features • Large LCD with blue backlight • Stylish appearance with hidden buttons • For 2 or 3 wires on-off controlled devices in 2-pipe FCU system (EXT-CF24-D202- •...
  • Page 2 LCD Electronic Thermostat EXT-CF24-D202-AF, EXT-CF24-D402-AF Maintenance mode Wiring Diagrams When the unit in “OFF” status, press “” for 5 seconds to enter maintenance mode. 24 VAC Press “” to change over from “disp > 0set > defr > usp > lsp”. If button is not pressed over 10 seconds, it will return to normal mode automatically.
  • Page 3 LCD Electronic Thermostat EXT-CF24-D202-AF, EXT-CF24-D402-AF Installation Manual Mounting Method open the clip with screw driver unplug the connector wiring mount it with screws plug in the connector close it with clip 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN...
  • Page 4 Canada Locations, 5845 Kennedy Road, Mississauga, Ontario L4Z 2G3 Tel. 866-805-7089, Fax 905-712-3124, marketing@us.belimo.com Latin America and the Caribbean Customer Service Tel. 203-791-8396, Fax 203-791-9139, marketing@us.belimo.com Belimo Brasil Comércio de Automação Ltda. Tel: 55 11 3643-5656, Fax: 55 11 3643 5657, atendimentoaocliente@br.belimo.com.

This manual is also suitable for:

Ext-cf24-d402-af