Quick Links

Technical Data
Power
AC 24V +10%, 50Hz/60Hz
Output signal
AC 24V x 2 (0.5A resistive)
EXT-RCP-24
0-10 VDC (5 mA) / 4-20 mA (600Ω)
Output signal
AC 24V x 2 (0.5A resistive)
EXT-RCF-24
fl oating point control
Input signal
dry contact (NO)
Dimensions
3.4" w x 3.4" h x 0.9" d [86mm x 86mm x 23mm]
Fixing screw width
60mm (standard)
Set temperature range
0° to 99.5° adjustable
Accuracy displayed
0.1°
Accuracy
+0.5°
Rated power
< 1W
Sensor type
NTC
Display
LCD
Basic Features
Working modes
Cooling
, Heating
Fan speed
3 speed ( Low
, Medium
Operation Instructions
On/Off
Press
button.
Setpoint
Press
to reduce the setpoint, press
in 0.5°C increments. The setpoint will be confi rmed automatically
after 5 seconds and then will return to display status. Press
to check setpoint.
Mode
Press
to change the working mode- Cooling
Vent
.
Fan speed
Press
to select the desired speed- low
or auto
. If single speed fan is chosen, only medium speed
be available.
Auto speed The fan speed will be changed automatically to the following:
Low speed- when room temperature is 1° difference with setpoint.
Med. speed- when room temperature is 2° difference with setpoint.
High speed- when room temperature is 3° difference with setpoint.
Sleep
Thermostat will go into sleep function after programming.
To set:
Press
button for 3 seconds until
will start in the center of the screen. Use
desired sleep time. The maximum setting is 48 hours. Thermostat
will return to working status after 5 seconds.
countdown. The setpoint will be replaced by the sleep setpoint.
To quit: When the thermostat is in sleep function,
to quit.
Keypad lock
Press
and
for 10 seconds. This will activate the
under this function, the keypad is locked. To unlock, press
for 10 seconds until
Set parameters
With thermostat off, press
all parameters.
800-543-9038 USA
1
, Ventilating
, Auto
, High
) / Auto
to increase the setpoint
, Heating
,
, medium
, high
display shows. A countdown
or
to adjust the
will fl ash to start
will fl ash. Press
or
display.
and
disappears.
for 10 seconds to enter the menu to set
866-805-7089 CANADA
Application
EXT-RC series of proportional and fl oating thermostats are used to control room
temperature in commercial applications.
Features
• LCD with green backlight
• Detects and displays room temperature
• On/Off capability of cooling and heating equipment
• Room temperature setting
• Fahrenheit (°F) or Celsius (°C) display
• Selectable single or three speed fan control
• Remote sensor input
Dimensions (mm)
or
,
will
LCD Electronic Thermostat
EXT-RCF-24, EXT-RCP-24
203-791-8396 LATIN AMERICA / CARIBBEAN

Advertisement

loading

Summary of Contents for Belimo EXT-RCF-24

  • Page 1 LCD Electronic Thermostat EXT-RCF-24, EXT-RCP-24 Application EXT-RC series of proportional and fl oating thermostats are used to control room temperature in commercial applications. Features • LCD with green backlight • Detects and displays room temperature • On/Off capability of cooling and heating equipment •...
  • Page 2 LCD Electronic Thermostat EXT-RCF-24, EXT-RCP-24 Parameter Settings Wiring Diagrams Parameter Description Default Range Power on status (0: off, 1: on, 2: hold) Fan speed (0: single speed, 1: three speed) Fan mode (DA: When the temperature reaches the set-point, the valve will close with the fan still running.
  • Page 3 LCD Electronic Thermostat EXT-RCF-24, EXT-RCP-24 Installation Manual Mounting Method Open the back panel with a screwdriver. Connect the wires per the wiring diagram. Secure the base with the screws provided. Reattach the front panel. 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN...
  • Page 4 Canada Locations, 5845 Kennedy Road, Mississauga, Ontario L4Z 2G3 Tel. 866-805-7089, Fax 905-712-3124, marketing@us.belimo.com Latin America and the Caribbean Customer Service Tel. 203-791-8396, Fax 203-791-9139, marketing@us.belimo.com Belimo Brasil Comércio de Automação Ltda. Tel: 55 11 3643-5656, Fax: 55 11 3643 5657, atendimentoaocliente@br.belimo.com.

This manual is also suitable for:

Ext-rcp-24