Carrier Comfort 48VT-C Owner's Information Manual page 8

Hide thumbs Also See for Comfort 48VT-C:
Table of Contents

Advertisement

To replace or inspect filters in accessory filter rack (See Fig. 2):
1. Remove the filter access panel using a 5/16- -in. nut driver.
2. Remove the filter(s) by pulling it out of the unit. If the
filter(s) is dirty, clean or replace with a new one.
When installing the new filter(s), note the direction of the airflow
arrows on the filter frame, which should be pointing at the indoor
coil.
3. Reinstall filter access panel ensuring opening is air and
watertight.
If you have difficulty locating your air filter(s) or have questions
concerning proper filter maintenance, contact your dealer for
instructions. When replacing filters, always use the same size and
type of filter that was supplied originally by the installer. See Table
1 for filter sizes supplied with accessory filter rack.
Replacing or inspecting filters in units with
economizers
Small Chassis (See Fig. 8)
1. Remove return air duct cover at rear of unit using a 5/16- -in.
nut driver.
2. Remove the filter(s) by pulling it out and through the unit
duct opening. If filter is dirty, replace both filters with new
ones.
When installing the new filters, note the direction of the airflow
arrows on the filter frame, which should be pointing at the indoor
coil.
3. Reinstall duct cover ensuring opening is air and watertight.
Large Chassis (See Fig. 9)
1. Remove filter access door using a 5/16- -in. nut driver.
2. Remove the filter(s) by pulling it out and through the unit
filter access door. If filter is dirty, replace both filters with
new ones.
Units with bent indoor coils, install 24 x 18 x 1 (610 x 457 x 25
mm) filter first and then install 24 x 16 x 1 (610 x 406 x 25) filter.
When installing the new filters, note the direction of the airflow
arrows on the filter frame, which should be pointing at the indoor
coil.
3. Reinstall filter access door ensuring opening is air and
watertight.
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in
damage.
Never operate your unit without filters in place. An
accumulation of dust and lint on internal parts of your unit
can cause loss of efficiency and blower motor and/or
compressor damage.
RETURN
DUCT COVER
(Remove for
filter access)
property
Fans and Fan Motors
Periodically check the condition of fan wheels and housings and
fan motor shaft bearings. Contact your dealer for the required
annual maintenance.
Indoor and Outdoor Coils
Cleaning of the coils should only be done by qualified service
personnel. Contact your dealer for the required annual
maintenance.
Condensate Drain
The drain pan and condensate drain line should be checked and
cleaned at the same time the cooling coils are checked by your
dealer.
Compressor
All compressors are factory shipped with a normal charge of the
correct type and quantity of refrigeration grade oil. A compressor
should rarely require additional oil.
8
SMALL CHASSIS
Fig. 8 - - Small Chassis Filter Access
LARGE CHASSIS
Fig. 9 - - Large Chassis Filter Access
A10063