Tescom DS340H User Manual page 33

Dsp controlled ups 40 - 60 - 80 kva 3 phase in - 3 phase out
Hide thumbs Also See for DS340H:
Table of Contents

Advertisement

R24 WAITING DC BUS
R25 BATTERY FAILURE
R26 BATT TEMP SENSOR
R27 BATT TEMP HIGH
R29 PFC RESET
R30 PLEASE WAIT
R31 RECTIFIER START
L01 TH1 TEMP HIGH
L02 TH2 TEMP HIGH
L03 TH1 TEMP LOW
L04 TH2 TEMP LOW
L05 FAN MAINT
L06 BATTERY MAINT
L07 OPT MAINTENANCE
L08 TH1 SENSOR FAIL
L09 TH2 SENSOR FAIL
L10 ENTER FAULT RESET
L11 BATT CB OPEN
L12 GENERAL MAINT
L13 PFC CAN COMM ERR
L14 INV CAN COMM ERR
INV CODE = 0XXX
A00 INV FAULT = XXXX
A01 O/P OVERCURRENT
A02 OVERTEMP SHUT
A03 BATT HIGH
A04 OUTPUT V.LOW
A05 OUTPUT V.HIGH
A06 OVERLOAD SHUT
A07 SHORT CIRCUIT
A08 ON MAINTENANCE
A09 MANUAL BYPASS
A10 BATTERY LOW SHUT
A11 REPO STOP
A12 DC BALANCE BAD
A13 PEAK CURRENT
A14 INV NOT START
A17 BYPASS FAILURE
A18 BYPASS VOLT
A19 BYP FREQ.TOLER
A20 OVERLOAD
A21 OVERTEMP
A22 OUTPUT OFF
A23 ON BYPASS
A24 REVERSE CURRENT
Warning
Rectifier is waiting DC BUS to raise for startup
Warning
Battery test failed
Warning
Battery temperature sensor is defected or not connected
Warning
Battery ambient temperature is high
Warning
Rectifier module power on
Warning
Rectifier waits as adjusted startup delay
Warning
Rectifier is in soft start stage
Panel module alarm codes
Warning
TH1 temperature is high
Warning
TH2 temperature is high
Warning
TH1 temperature is low
Warning
TH2 temperature is low
Warning
FAN maintenance time
Warning
Battery maintenance time
Warning
Optional maintenance time
Warning
TH1 temperature sensor failure
Warning
TH2 temperature sensor failure
Warning
UPS is waiting fault reset for startup
Warning
External interactive battery switch is off
Warning
General maintenance time
Warning
PFC module CAN communication timeout
Warning
INV module CAN communication timeout
Inverter module alarm codes
Current inverter modüle status code
Hata
XXXX fault occured at the inverter module
CALL SERVICE !
Alarm
IGBT saturation alarm on inverter module
Alarm
Overtemperature at inverter power module
Alarm
Inverter module measured battery voltage high
Alarm
Inverter output voltage is low
Alarm
Inverter output voltage is high
Alarm
Overload at UPS output
Alarm
Short circuit at UPS output
Alarm
Maintenance by-pass switch on
Alarm
Load is transferred to by-pass from front panel
Alarm
Inverter measured battery voltage is low (shutdown level)
Alarm
External REPO input signal sensed
Alarm
Before inverter start fitler capacitors dont discharged
Alarm
Very high current at the UPS output
Alarm
Inverter module start failed
Warning
By-pass input voltage failure
Warning
By-pass input voltage out of tolerance
Warning
By-pass input frequency out og tolerance
Warning
Currently the load exceeded 100% capacity
Warning
Currently inverter power modul heatsink temperature is high
Warning
There is no UPS output voltage
Warning
Load is on bypass
Warning
Regenerative backfeed to UPS output
31