Tescom DS300SHPA Series User Manual page 55

Dsp controlled ups (pf:0.8) 3-phase in / 3-phase out
Table of Contents

Advertisement

823 Status code
Status
Inverter alarm
Description
MASTER frequency exceeded maximum limit ,inverter stopped
İf master frequency is okay automatic
Restart
Returning to fault
--
Check the followings:
-Check each UPS output frequency selection in parallel system
824 Status code
Status
Inverter alarm
Description
MASTER DC voltage zone 7,My DC voltage zone 1 inverter down
İf mains input voltage is okay automatic
Restart
Returning to fault
--
Check the followings:
-Check the mains input power of the UPS
- If input power is OK wait until batteries are fully charged
- If the mains input power is shurdown check the other UPSs mains input power (in parallel system if the
same A/H rating batteries are used at each UPS the battery discharge timebe same for each UPS) If the
other UPS is continue to run check the batteries of this UPS.
-Call service
825 Status code
Status
Inverter alarm
Description
SLAVE DC voltage zone 7,My DC voltage zone 1 inverter down
İf mains input voltage is okay automatic
Restart
Returning to fault
--
Check the followings:
-Check the mains input power of the UPS
- Check the battery status of this UPS
- Call service
826 Status code
Status
Inverter alarm
Description
MASTER DC voltage zone 7,My DC voltage zone 1 trying to join system
İf mains input voltage is okay automatic
Restart
Returning to fault
--
827 Status code
Status
Inverter alarm
Description
SLAVE DC voltage zone 7,My DC voltage zone 1 trying to join system
İf mains input voltage is okay automatic
Restart
Returning to fault
--
53