Download Print this page

Goldline SP-33 Quick Start Manual

Single stage temperature control

Advertisement

Quick Links

The SP-33 and SP-33D controls are single stage,
general purpose, temperature controls for use in
HVAC, refrigeration, and industrial applications.
The setpoint temperature range is user selectable
from:
40°F to +104°F
The SP-33 control provides one isolated SPDT
relay output while the SP-33D provides two (ef-
fectively DPDT). The relays on both the SP-33
and SP-33D are controlled by comparing the
thermistor temperature sensor to the adjustable
setpoint temperature. The user can select either
"heat" mode (relay operates on temperature fall)
or "cool" mode (relay operates on temperature
rise). The control setpoint can be set using the
Power:
Approx. 2VA required from any power
source:
21-27VDC
21-27VAC, 50/60Hz
105-130VAC, 50/60Hz
195-250VAC, 50/60Hz
Outputs: SPDT isolated (dry)contacts,
1HP@115VAC, 2HP@240VAC
rating @ 240VAC:
20A on NO contacts
10A on NC contacts
internal setpoint dial (factory setting) or a remote
setpoint dial (see Goldline RSP-33 remote set-
point on page 7). The SP-33 and SP-33D also
features a plug in connector for a TD-30 Digital
Display Monitor. The TD-30 snaps into the cover
for easy mounting and displays both sensor and
setpoint temperatures.
Power can be provided from a 24VAC, 24VDC,
115VAC or 240VAC power source. Relay con-
tacts are completely isolated so the outputs can
switch any voltage, regardless of the power source.
On SP-33D models, one relay output can switch
high voltage, the other switch low voltage. A
movable divider is provided to separate high and
low voltage wiring compartments.
Sensors: Thermistor, 10K @ 25°C/77°F
Type SW supplied with control
Interchangeable with any IE
temperature sensor
1000 ft. maximum wire run
Setpoint:
40 to +104°F
Differential:
1-25°F
Accuracy:
+/- 1°F
Environment: -30 to +130°F
0-95% rH, non-condensing

Advertisement

loading
Need help?

Need help?

Do you have a question about the SP-33 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Goldline SP-33

  • Page 1 (see Goldline RSP-33 remote set- HVAC, refrigeration, and industrial applications. point on page 7). The SP-33 and SP-33D also The setpoint temperature range is user selectable features a plug in connector for a TD-30 Digital from: Display Monitor.
  • Page 2 Page 2 Setup The SP-33 and SP-33D can be configured to before attempting to install or wire the control. operate in a variety of applications using jumpers The jumper functions and appropriate positions located on the circuit board (see diagram below).
  • Page 3 Page 3 Mounting sensor supplied with the control does not meet The SP-33 and SP-33D controls are designed for your needs, contact your distributor for informa- mounting indoors, protected from the weather and tion on the wide range of interchangeable Gold- with non-condensing humidity.
  • Page 4 Page 4 Output wiring SP-33D: The SP-33D provides two sets of iso- SP-33: The SP-33 provides one set of isolated lated SPDT relay outputs. If you are directly SPDT relay outputs. If you are directly control- controlling a load (eg pump, blower, valve, etc),...
  • Page 5 LEDs (output relay(s) turn off). The output relay(s) are The SP-33 and SP-33D use 2 LED indicators to only allowed to energize AFTER the timer has display the status of the control. The diagram on completed counting. If the timer hasn't finished page 2 shows the location of each LED.
  • Page 6 RSP-33. See included in- structions for mounting information. The RSP-33 Adjustments uses a 3 conductor connection to the SP-33/33D Adjust the setpoint and differential to the desired controls. A 3 position screw terminal block on the settings.
  • Page 7 For a given temperature, the resistance is All Goldline controls use 10K thermistor sensors. accurate to +/- 1%. For a given resistance the When disconnected from the control, the sensor temperature is accurate to +/- 0.5°F.

This manual is also suitable for:

Sp-33d